FIRE  DETECTION  SYSTEM

XLs Loaded: Dec 08 2016
Compiled Revision # 98, by: Deputy Fire Safety Director Gordon A. Roy ; 28 June 2017


Recent Revision History :

rev 73 - 10 Feb 2010 remove address 2-002-025 : Smoke Detector on underside of P-Hall TISOL platform permanently removed due to re-construction
                     update the following MXL Graphics maps to reflect recent construction: MOB G & L1, ISAC TMB G and P-Hall G.
rev 82 - 29 Feb 2012 add addresses: 2-001- -010, -011. -020, -021, -023 & 2-002-053
rev 83 - 17 Jul 2012 add addresses: 2-001-059, 2-001-060 MHESA RCR Lab Sprinklers , 5-052-060 Francium Room Duct Smoke
rev 84 - 14 Nov 2012 add E-Linac Compressor Building into the system. Node 8, loops 41 & 42
rev 85 - 13 Sep 2013 add ARIEL Building into the system. Node 9, loops 91, 92, 93, 94
rev 86 - 27 Jan 2014 remove devices from BL4 North, address 2-001-040 for construction, TRI terminated with EOL
rev 87 - 23 Oct 2014 updating descriptions for ARIEL and Compressor Building
rev 88 - 08 Nov 2014 updating 1-035-023 & 1-035-031 and adding 1-035-030 (MOB AHU #5)
rev 89 - 24 Jan 2015 adding 9-093-037 & 9-093-038, sprinkler devices for ARIEL G-04 (Paint Booth) and L2-06 (Shaft Room, SE corner)
rev 90 - 06 Feb 2015 removing TRI 2-001-040 no longer needed & adding 2-002-025 E-Hall Exhaust Duct Smoke deteector
rev 91 - 09 Dec 2015 formatting for increased visibility
rev 92 - 10 Dec 2016 add Node Map and numerous changes due to upgrade from MXL to XLS
rev 93 - 27 Feb 2017 Changing addresses as a result of upgrade from MXL to XLS
rev 94 - 30 May 2017 add addresses 2-001-024 MHESA L1 Clean Rm Duct Smoke and 2-001-040 MHESA L1 Clean Rm Fan Shutdown
                     Updating some document formatting as a result of upgrade from MXL to XLS
rev 95 - 09 Jun 2017 change add address 3-019-021 from “CA B1 MAIN SPRINK.SUPPLY : FS, PS & TS” to “CA B1 MAIN SPRINK SUPPLY FLOW” following the
                     removal of the old valve and pressure switch and the addition of a new Flow Switch.
                     add address 3-019-023 “CA B1 MAIN SPRINKLER TAMPER” following the installation of a new main valve.
rev 96 - 19 Jun 2017 add addresses 9-091-030, 9-091-031, 9-091-032, 9-091-033 ARIEL/ISAC link smoke detectors and manual pull stations
rev 97 - 26 Jun 2017 Swap Monitoring Zones 1 & 2 so that Zone 1 now corresponds to Node 1 and Zone 2 now corresponds to Node 2 (+3,4,7,8)
rev 98 - 28 Jun 2017 remove 1-035-007, 1-035-008; change 1-035-005 & 1-035-006,; add 1-035: -051 through -059

rev - next



TABLE OF CONTENTS




TRIUMF - FIRE ALARM SYSTEM

INTRODUCTION

The twenty four character device messages that appear on the LCD display are consistently coded in the following manner :

Address , Building , Level , Other Location , Device type

Note: "Other Location" and "device type" may not always be present

The address and message are followed by a more complete and descriptive section of text. The text may contain information such as how to locate the actual detector or TRI, or what other action occurs if this detector alarms (eg fan shutdown).

Some typical examples of each section of the description are as follows:


EXAMPLE : 5-052-043 ISAC TMB L1 E. EMRG DOOR MS

NOTES:

1. Loop numbers are not duplicated on different Nodes/Panels therefore panel number is not required for device identification.
2. All devices are labeled with their unique loop and device number. (ie. 052-043)
3. Any device removed or wiring disconnected will result in a "Trouble" being annunciated indicating the address of the device or zone.

    ALL input devices can initiate an ALARM except where noted as TROUBLE or SUPERVISORY.

This document is under constant review and is subject to upgrading and expansion. Refer to Revision number and Compiled date to ensure a recent version.
This document has been carefully prepared and verified to ensure correctness. However some unknown errors may exist. Please inform the author if any are observed.


ABBREVIATIONS :



CROSS REFERENCES :


LOOP ADDRESS & AREA