T R I U M F
FIRE DETECTION SYSTEM
TABLE OF CONTENTS
TRIUMF - FIRE ALARM SYSTEM
INTRODUCTION
The twenty four character device messages that appear on the LCD display are consistently coded in the following manner :
Address , Building , Level , Other Location , Device type
Note: "Other Location" and "device type" may not always be present
The address and message are followed by a more complete and descriptive section of text.
The text may contain information such as how to locate the actual detector or TRI, or what other action occurs if this detector alarms (eg fan shutdown).
Some typical examples of each section of the description are as follows:
EXAMPLE : 5-052-043 ISAC TMB L1 E. EMRG DOOR MS
" 5-052-043 " . . System Address of device (1st digit = XLS # (Node/Panel #), 2nd group = loop #, 3rd group = device address #)
" ISAC " . . . . ISAC building complex
" TMB " . . . . . Target Maintenance Building
" L1 " . . . . . Level 1, one floor above ground
" E " . . . . . . Easterly portion of the floor
" EMRG DOOR " . . Emergency door
" MS " . . . . . Pull Station , (the Device type is "MS" for Manual (pull) Station)
The Other Information english description is :
"Pull Station, door 99, East Design Office, door to East Emergency Exit stairs"
NOTES:
1. Loop numbers are not duplicated on different Nodes/Panels therefore panel number is not required for device identification.
ALL input devices can initiate an ALARM except where noted as TROUBLE or SUPERVISORY.
This document is under constant review and is subject to upgrading and expansion. Refer to Revision number and Compiled date to ensure a recent version.
ABBREVIATIONS :
CROSS REFERENCES :
Node LOOP AREA
1- 034-035- . . Main Office Bldg
2- 001- . . . . Haz.Mat Bldg
2- 002- . . . . Machine Shop
2- 003- . . . . various bells
2- 007- . . . . Service Annex
3- 019- to 023- Chemistry Annex (RCA 1 & 2)
4- 026-, - 028- RCA3
5- 051- to 057- ISAC 1
6- 061- to 068- ISAC II
7- 013- to 015- Stores & Design Office Facility
8- 041-, 042- & 043- Compressor Building for e-Linac
9- 091- to 097- ARIEL
12- 110 Plant Vacuum Bldg.
LOOP ADDRESS & AREA
XLS# XLS, PMI-2 & SSD-C Locations :
ALARM ADDRESSES TO TRANSPONDER:
1-034-003 OUTSIDE FENCE ALARMS. . ZONE 1 . Alarm to Transponder . Relay in MOB XLS , Node 1
1-034-004 INSIDE FENCE ALARMS . . ZONE 2 . Alarm to Transponder . Relay in MOB XLS , Nodes 2,3,4,7,8
1-034-002 ISAC or ISACII ALARMS . ZONE 3 . Alarm to Transponder . Relay in MOB XLS , Nodes 5 & 6
1-034-001 ARIEL ALARMS  . . . . . ZONE 4 . Alarm to Transponder . Relay in MOB XLS , Node 9
TRIUMF - FIRE ALARM SYSTEM
DEVICE ADDRESSES LISTED BY LOOP NUMBER [ Note: The Loop number is the second set of numbers : Panel - Loop - Device]
M8 BUILDING
M-15 BUILDING
HAZARDOUS MATERIALS STORAGE BUILDING
TRI - in Lobby on West Wall
SERVICE ANNEX (also 2-007-001 - 008-055) MESON HALL EXTENSION SERVICE ANNEX
ELECTRON HALL
2-001-099 ELECTRON HALL B2 SE PS . . . MS . . . Pull Station on South Wall at door
SERVICE ANNEX - continued
Compiled Revision # 107, 07 May 2022
Recent Revision History :
rev 84 - 14 Nov 2012 add E-Linac Compressor Building into the system. Node 8, loops 41 & 42
rev 85 - 13 Sep 2013 add ARIEL Building into the system. Node 9, loops 91, 92, 93, 94
rev 86 - 27 Jan 2014 remove devices from BL4 North, address 2-001-040 for construction, TRI terminated with EOL
rev 87 - 23 Oct 2014 updating descriptions for ARIEL and Compressor Building
rev 88 - 08 Nov 2014 updating 1-035-023 & 1-035-031 and adding 1-035-030 (MOB AHU #5)
rev 89 - 24 Jan 2015 adding 9-093-037 & 9-093-038, sprinkler devices for ARIEL G-04 (Paint Booth) and L2-06 (Shaft Room, SE corner)
rev 90 - 06 Feb 2015 removing TRI 2-001-040 no longer needed & adding 2-002-025 E-Hall Exhaust Duct Smoke deteector
rev 91 - 09 Dec 2015 formatting for increased visibility
rev 92 - 10 Dec 2016 add Node Map and numerous changes due to upgrade from MXL to XLS
rev 93 - 27 Feb 2017 changing addresses as a result of upgrade from MXL to XLS
rev 94 - 30 May 2017 add addresses 2-001-024 MHESA L1 Clean Rm Duct Smoke and 2-001-040 MHESA L1 Clean Rm Fan Shutdown
Updating some document formatting as a result of upgrade from MXL to XLS
rev 95 - 09 Jun 2017 change add address 3-019-021 from “CA B1 MAIN SPRINK.SUPPLY : FS, PS & TS” to “CA B1 MAIN SPRINK SUPPLY FLOW” following the
removal of the old valve and pressure switch and the addition of a new Flow Switch.
add address 3-019-023 “CA B1 MAIN SPRINKLER TAMPER” following the installation of a new main valve.
rev 96 - 19 Jun 2017 add addresses 9-091-030, 9-091-031, 9-091-032, 9-091-033 ARIEL/ISAC link smoke detectors and manual pull stations
rev 97 - 26 Jun 2017 swap Monitoring Zones 1 & 2 so that Zone 1 now corresponds to Node 1 and Zone 2 now corresponds to Node 2 (+3,4,7,8)
rev 98 - 28 Jun 2017 remove 1-035-007, 1-035-008; change 1-035-005 & 1-035-006,; add 1-035: -051 through -059
rev 99 - 27 Nov 2017 updated "Sprinkler Valves and Devices" section to reflect changes made in rev 98
rev100 - 17 May 2018 updating to show changes in ARIEL C.S.B. - removing add 9:091-023 & 9:091-024 and replacing with 9:098-001 (two smoke, now one linear beam)
rev101 - 03 Jun 2018 general updating to show changes: remove 3-020-030 (not in use) , change text for 1-035-010
rev102 - 03 Feb 2019 change "Nordion" (or "NORD") to RCA3, Bell cadence changed from "continuous" to "Temporal 3" (T-3) Annual Verification completed for 2019
rev103 - 01 May 2019 add address: 9-091-019 "ARIEL G N ALIS Rm HVAC Duct" Duct Detector
rev104 - 15 Sep 2020 Remove “9-094-008 ARIEL B2 S, TGT ASSY W SMK B2 South, Target Assembly Lab, West” due to room modifications
rev105 - 28 Feb 2020 Updating text. Adding "HazMat" to "Devices Listed By Area" selection
REV 2022 Incorporating changes due to 2021/2022 device upgrade
rev106 - 15 Apr 2022 add Plant Services Building, loop #095
rev107 - 07 May 2022 Change Plant Services Building loop number from 095 to 110 to corrrect Siemens mistake
XXX
rev - next
001
002
003-004
007
008
013-015
019
020
023
027
028
033-035
036
037-038
041-042
051
052
053-059
061
062
063+
091+
095
110
ARIEL
CA
CA & MH
E-Comp.Bldg.
HazMat
ISAC 1
ISAC II
M-8
M-15
M.S.
MH pt1
MH pt2
MHESA
MOB
PSB
RCA3
RH
SA pt1
SA pt2
SDF
Tlr Gg
Tlr Hh
2. All devices are labeled with their unique loop and device number. (ie. 052-043)
3. Any device removed or wiring disconnected will result in a "Trouble" being annunciated indicating the address of the device or zone.
This document has been carefully prepared and verified to ensure correctness. However some unknown errors may exist. Please inform the author if any are observed.
A . . . . . . Application Specific Device (detector: duct, transformer etc.)
AHU . . . . . Air Handling Unit
ARL . . . . . ARIEL - Advanced Rare IsotopE Laboratory
B . . . . . . Bell
Bn . . . . . floor Below ground level, Bn (B1, B2, B3)
C . . . . . . Centre
CA . . . . . Chemistry Annex - RCA 1 & 2 (also see RCA 3)
CI . . . . . Contact Input (often to a TRI module)
CO . . . . . Contact Output (often from a TRI module)
COMP . . . . Compressor Building for e-Linac
CZM . . . . . Conventional Zone Module (monitors "non-intelligent" detectors)
DS . . . . . Duct Smoke Detector
DR . . . . . Door
E . . . . . . East
EComp . . . . E-Linac Compressor Building
ELEV . . . . Elevator
EL . . . . . Elevator
ELR . . . . . End of Line Resistor
EMERG . . . . Emergency
EXPHAL . . . Experimental Hall (ISAC)
F . . . . . . Fixed temperature heat detector (not testable)
FLR . . . . . Floor
Fn . . . . . Panel Function keys (F1, F2, F3, F4, Alt1 F1, Alt2 F1 etc.)
FS . . . . . Flow Switch (Sprinkler system)
G or GND . . Ground level
GA . . . . . General Alarm Key Source
HAZMAT . . . Hazardous Materials (building)
HD . . . . . Heat Detector (rate of rise unless type "F")
I . . . . . . Ionization detector or contact Input (see CI)
ISAC N . . . ISAC North (Experimental Hall)
ISAC S . . . ISAC South (see "TMB", Service Building and Design Office)
ISAC2 . . . . ISACII buildings (note: "II" not acceptable in programming)
Ln . . . . . floor Level above Ground, Ln (L1, L2, L3)
MACH . . . . Machine
MH . . . . . MESON Hall
MHE . . . . . MESON Hall Extension
MHESA . . . . MESON Hall Extension Service Annex
MOB . . . . . Main Office Building
MS . . . . . Manual Station (manually operated Pull Station)
N . . . . . . North
OFF . . . . . Office
P . . . . . . Photoelectric detector
PA . . . . . Photoelectric Application Specific Device (detector)
PH . . . . . Proton Hall
PHE . . . . . Proton Hall Extension
PMI-2 . . . . Person Machine Interface-2 (for Siemens XLS)
PS . . . . . Pull Station (see also MS) or Power Supply
RCA . . . . . Radio Chemistry Annex 1, 2 or 3 (note: for RCA 1 & 2 see CA)
RCA 3 . . . . Radio Chemistry Annex north building (1 & 2 are south)
RM . . . . . Room
RTU . . . . . Roof Top Air Handling Unit
S . . . . . . South
SA . . . . . Service Annex
SAE . . . . . Service Annex Extension
SDF . . . . . Stores & Design office Facility
SMK . . . . . Smoke Detector (ionization type unless "P", "PA" or "SMKB")
SMKB . . . . Smoke Detector Linear Beam
SOL . . . . . Solenoid (electrically controlled sprinkler system valve)
SPRNK . . . . Sprinklers
SSD-C . . . . System-Status Display with Control (for Siemens XLS)
SV . . . . . Solenoid Valve
TMB . . . . . Target Maintenance Building (official name of the ISAC South bldg. complex)
TRI . . . . . Trasnponder Remote Intelligent, interface module (input (CI) or output (CO))
TS . . . . . Tamper Switch (Sprinkler system)
V . . . . . . Visual Alarm Device (strobe)
VESDA . . . . Very Early Smoke Detection Apparatus
W . . . . . . West
WC . . . . . Water Closet (washroom)
ZONE . . . . Monitoring company Zone information; see "ALARM AND TROUBLE ADDRESSES TO TRANSPONDER"
AREA ZONE LOOP ADDRESSES
ARIEL 4 9: 091- to 095-
Chemistry Annex (RCA 1&2) 2 3: 019- to 022-
E-Compressor Bldg 2 8: 041 and 042
Hazardous Materials Bldg 2 2: 001-
ISAC 1 3 5: 051- through 059-
ISAC 2 3 6: 061- through 068-
M-8 Bldg (CMMS) 2 2: 001-
M-15 Bldg 2 2: 001-
Machine Shop 2 2: 002-
Main Office Bldg 1 1: 034-, 035-, 037-
MESON Hall 2 3: 020- and 021-
MHESA 2 2: 001-
Plant Vacuum building 2 12: 110
Proton Hall (e-Hall) 2 2: 001- and 002-
Proton Hall Ext. 2 2: 002-
RCA 3 2 4: 027- and 028-
Remote Handling Bldg 2 2: 002-
Service Annex 2 2: 001-, 007-, 008-, 009-, 017-
Service Annex Extension 2 2: 002- and 007-
Stores & Design Office 2 7: 011- 014-
Trailer Gg 2 2: 002-
Trailer Gg Extension 2 2: 002-
Trailer Hh 1 1: 036-
036- . . . . Trailer Hh
037- . . . Bell Circuits
001- . . . . M-8 Bldg
001- . . . . M-15 Bldg
001- . . . . MHESA
001- . . . . Proton Hall
001- . . . . Service Annex
002- . . . . Proton Hall
002- . . . . Proton Hall Ext
002- . . . . Remote Handling Bldg
002- . . . . Service Annex Ext
002- . . . . Trailer Gg
002- . . . . Trailer Gg Ext
007- . . . . Service Annex Extension
2- 008- . . . . Service Annex
020- to 021- MESON Hall
023- Chemistry Annex (RCA 1&2) Led's
2- 001-
2- 002-
2- 003-
2- 007-
2- 008-
3- 003
3- 019- to 021-
3- 023-
4- 026-, 027-, 028-
1- 034-, 035-
1- 036-
1- 037-
5- 051- to 057-
6- 061- to 068-
7- 013 to 015-
8- 041-, 042- & 043-
9- 091- to 097-
12- 110-
1 - Main Office Bldg - PMI-2 ( GLOBAL ) in XLS panel, Lobby, SE corner
2 - Service Annex - PMI-2 in XLS panel, Service Annex B2, West wall
Service Annex - PMI-2 ( GLOBAL ) in Main Control Room, rear of rack "A"
3 - Chemistry Annex - PMI-2 in XLS, CA L2, South Penthouse, West wall
Chemistry Annex - SSD-C, CA G South, at door #11 (adjacent to map panel)
4 - RCA3 - SSD-C in XLS panel, RCA3 Bldg., B1, Electrical Room #050, East wall
RCA3 - PMI-2 ( GLOBAL ) in Graphics Panel, Lobby, Ground floor near West door
5 - ISAC 1 - PMI-2 in XLS panel, ISAC TMB B1, Lobby
ISAC 1 - SSD-C in South stairwell, Target Maintenance Building, Ground floor, South side
ISAC 1 - SSD-C in ISAC Experimental Hall, South centre, near door #117
6 - ISAC II - PMI-2 in XLS panel, Electrical Room, Ground floor, room #165, East end of North wall
ISAC II - SSD-C in Graphics Panel, Lobby Entrance, Ground floor, West side of building
ISAC II - SSD-C in Control Room, L1 room #245, North wall
7 - SDF - PMI-2 in XLS panel, Ground floor, North East staircase, room west of Lobby
8 - Compressor Bldg. - PMI-2 in XLS panel, Ground Floor, East wall of Compressor Room
9 - ARIEL - PMI-2 in XLS Panel, B1 North, Electrical Services Room
ARIEL - SSD-C in South Lobby (#1)
ARIEL - SSD-C in North Lobby (#2)
12 - Plant Vacuum Bldg. - PMI-2 in XLS Panel, Plant Workshop NE corner
MESON HALL EXTENSION SERVICE ANNEX (MHESA)
2-001-001 . MHESA B1 FLOOR, BSMT . . HD. . . Elevator Machine Room
2-001-002 . MHESA B1 FLOOR, BSMT . . MS. . . Pull Station, West end of hall
2-001-003 . MHESA B1 FLOOR, BSMT . . SMK . . Room 4
2-001-004 . MHESA B1 FLOOR, BSMT . . SMK . . Room 5
2-001-005 . MHESA B1 FLOOR, BSMT . . SMK . . Room 1B
2-001-006 . MHESA B1 FLOOR, BSMT . . SMK . . Room 1A
2-001-007 . MHESA B1 FLOOR, BSMT . . SMK . . Room 3
2-001-008 . MHESA B1 FLOOR, BSMT . . MS. . . Pull Station, East end of hall
2-001-009 . MHESA B1 FLOOR, BSMT . . SMK . . Room 6 West
2-001-010 . MHESA B1 FLOOR, BSMT . . SMK . . Room 6 East
2-001-011 . MHESA B1 HALLWAY WEST. . SMK . . West end of Hallway
2-001-012 . MHESA B1 HALLWAY EAST. . SMK . . East end of Hallway
the following two addresses need to be checked
2-001-010 . . MHESA B1 RCR LAB WEST . . . SMK . . West side of lab, door # 06A
2-001-011 . . MHESA B1 RCR LAB EAST . . . SMK . . East side of lab, door # 06B
2-001-014 . MHESA GROUND FLOOR S . . SMK . . Assembly area , South West
2-001-015 . MHESA GROUND FLOOR W . . SMK . . Assembly area , West, Above room 13, Janitor
2-001-016 . MHESA GROUND FLOOR C . . SMK . . Assembly area , South Centre
2-001-018 . MHESA GROUND FLOOR SE . SMK . . Assembly area , South East
2-001-017 . MHESA GROUND FLOOR N . . SMK . . Assembly area , North Centre , by North doors
2-001-019 . MHESA GROUND FLOOR NE . SMK . . Assembly area , North East , above room 16
2-001-020 . MHESA GROUND FLOOR PS . MS. . . Pull Station, door 76, South West
2-001-021 . MHESA GROUND FLOOR PS . MS. . . Pull Station, door 78, East
2-001-022 . MHESA GROUND FLOOR PS . MS. . . Pull Station, door 19, South East
2-001-023 . MHESA L1 FLOOR EAST. . . SMK . . East end of hall by Room 32
2-001-024 . MHESA L1 FLOOR CEBTRE. . SMK . . Centre of hall by room 28
2-001-025 . MHESA L1 FLOOR WEST. . . SMK . . West end of hall by Elevator
2-001-026 . MHESA L1 FLOOR RM 34 . . SMK . . Room 34
2-001-027 . MHESA L1 FLOOR RM 35 . . SMK . . Room 35 , enter via room 34
2-001-028 . MHESA L1 FLOOR PS . . . . MS . . Pull Station at East door
2-001-029 . MHESA L1 FLOOR PS . . . . MS . . Pull Station at West door
2-001-030 . MHESA L1 TOP OF W STAIR . SMK. . Top of West Stairs
2-001-031 . MHESA L1 TOP OF E STAIR . SMK. . Top of East Stairs
2-001-032 . MHESA L1 TOP ELEV.SHAFT . SMK. . Top of Elevator Shaft (tested from L1 level)
2-001-033 . MHESA L1 RCR FILTER RM. . SMK. . L1, RCR Filter Room, enter via door 34, then door 35
2-001-034 . MHESA L1 CLEAN RM DUCT . . DS. . Duct Detector is in Room 34 in the return duct of
the HVAC for the Clean Room. Note: also activates 2-001-098 MHESA L1 CLEAN RM FAN SHUTDOWN
TRI - MHESA L1, room 34, on North wall
2-001-035 MHESA ELR #1 . . . . . . . CO . . Room 34, Clean room, Exhaust Fan Shutdown
TRI - MHESA L1, room 34, on North wall
2-001-036 MHESA ELR #2 . . . . . . . CO . . Room 34, Clean room, Supply Fan Shutdown
TRI - ground level, South West, near door 76
2-001-037 MHESA GAS SHACK HEAT/PUL
- module monitoring the following 2 devices -
2-001-013^1 . MHESA B1 RCR SPRNK FLOW . . FS . . Flow switch for RCR Lab sprinklers. Located in room 03
2-001-013^2 . MHESA B1 SPRINKLER TAMPER . TS . . Either of two Backflow Preventer Valves located in room 03 = SUPERVISORY
2-001-039 M-8 G TOP OF S STAIRS . . SMK . . Top of South stairwell near door 6, South entrance
2-001-040 M-8 G EAST STAIRS, EMRG . SMK . . East Emergency Exit stairwell, top hatchway opens up to outside, East of M-8 building
2-001-041 M-8 G ELEVATOR SHAFT . . .SMK . . Top of Elevator Shaft, L1, visible with elevator car at ground floor, between car and door frame
(label on ground floor door frame)
2-001-042 M-8 L1 DUCT: A.C.RETURN . DS . . Roof Level A.C. Return Duct, on East side of unit
2-001-043 M-8 B2 FLOOR . . . . HD F . Room 104, Patient Treatment room
2-001-044 M-8 B2 FLOOR . . . . MS . . Pull Station, at door by Room 104
2-001-045 M-8 B2 FLOOR . . . . HD . . Room 103, Bio Medical Research Control Room
2-001-046 M-8 B2 FLOOR . . . . HD . . Room 108, old X-Ray Room (inside Room 101)
2-001-047 M-8 B2 FLOOR . . . . HD . . Room 101, entrance hall to X-Ray and Darkroom
2-001-048 M-8 B2 FLOOR . . . . HD . . old Darkroom (inside Room 101)
2-001-049 M-8 B2 FLOOR . . . . HD . . Room 102, Washroom
2-001-050 M-8 B2 FLOOR . . . . HD F . Room 107, Elevator Machine Room
2-001-051 M-8 B2 FLOOR . . . . MS . . Pull Station, at South stairs
2-001-052 M-8 B1 FLOOR . . . . HD F . Room 203 , ex-power supply room
2-001-053 M-8 B1 FLOOR . . . . HD . . Room 202 , workshop & service area
2-001-054 M-8 B1 FLOOR . . . . MS . . Pull Station, Room 202, at East emergency Stairs
2-001-055 M-8 B1 FLOOR . . . . HD . . Room 206 , Office
2-001-056 M-8 B1 FLOOR . . . . MS . . Pull Station, By South stairs
2-001-057 M-8 B1 FLOOR . . . . HD . . Room 204 , Office
2-001-058 M-8 B1 FLOOR . . . . HD . . Room 205 , Janitor room & Hot Water Heater
2-001-059 M-8 B1 FLOOR . . . . HD . . Room 201 , Office
2-001-060 M-8 B1 FLOOR . . . . HD . . Hallway
2-001-061 M-8 GROUND FLOOR . . HD . . Room 301 , Office, South side, enter via Room 302
2-001-062 M-8 GROUND FLOOR . . HD . . Room 302 , Offices, West side
2-001-063 M-8 GROUND FLOOR . . HD . . Room 303 , Office, West Centre area
2-001-064 M-8 GROUND FLOOR . . HD . . Room 304 , North West corner area
2-001-065 M-8 GROUND FLOOR . . HD . . Room 305 , Office, North Centre area
2-001-066 M-8 GROUND FLOOR . . HD . . Room 306 , Office, North East area
2-001-067 M-8 GROUND FLOOR . . HD . . Room 307 , Office, East side
2-001-068 M-8 GROUND FLOOR . . HD . . Room 312 , West detector
2-001-069 M-8 GROUND FLOOR . . HD . . Room 312 , East detector, by door 7
2-001-070 M-8 GROUND FLOOR . . HD . . Room 308 , Washroom, at Main Entrance
2-001-071 M-8 GROUND FLOOR . . HD . . Room 310 , Main Entrance hallway, (door 6, South)
2-001-072 M-8 GROUND FLOOR . . MS . . Pull Station , Main Entrance (South) Hallway
2-001-073 M-8 GROUND FLOOR . . MS . . Pull Station , door 7, East door, Inside Room 312
2-001-074 M-8 GROUND FLOOR . . MS . . Pull Station , door 5, West door, Inside Room 304
TRI - on East side of MCC-M, (MESON Hall)
2-001-075 M-8 ELR . . . . . . . . . CO . . M8 HVAC Fans Shutdown , TROUBLE Only
2-001-076 M-15 BUILDING . . . . MS . . Pull Station, door 26, South
2-001-079 M-15 BUILDING . . . . MS . . Pull Station, door 27, North East
2-001-077 M-15 BUILDING . . . . MS . . Pull Station, door 28, West
2-001-078 M-15 BUILDING . . . . MS . . Pull Station, at North West door (mezzanine)
2-001-080 M-15 BUILDING . . . . HD F . Room 101 , equipment room
2-001-081 M-15 BUILDING . . . . HD . . Room 102 , counting room
2-001-082 M-15 BUILDING . . . . HD . . Roof Level, Centre
2-001-083 M-15 BUILDING . . . . HD . . Roof Level, North, above power supplies
2-001-084 HAZ.MAT.BLDG SPRINKLERS . . FS . . Sprinkler water flow, and fan shutdown relay
TRI - in Lobby on West wall
2-001-085 HAZ.MAT. BLDG
- module monitoring the following 5 devices -
- module also operates the following 2 devices -
2-001-086 SA B1 PLANT WORKSHOP. . . HD . . Room 06, East of Emergency Generator
2-001-087 SA B1 HOLDING TANK ROOM . HD . . Room 07, South of Emergency Generator
2-001-088 SA B1 MAGNETS PS SHOP . . HD . . Room 08, between Plant Workshop & RF Room
2-001-089 SA B1 MENS WASHROOM . . . HD . . Room 02, in West stairwell
2-001-090 SA B1 W STAIRS PULL STN . MS . . Pull Station, between elevator & West stairwell door
2-001-091 SA B1 E STAIRS PULL STN . MS . . Pull Station, at East stairwell door by R.F. Console
TRI - between elevator & West stairwell door
2-001-092^1 SA B1 W AREA HEAT (8)
- module monitoring the following 8 devices -
TRI - between elevator & West stairwell door
2-001-092^2 SA B1 RF ROOM HEAT (7)
- module monitoring the following 7 devices -
2-001-093 SA B2 W STAIRS PULL STN . MS . . Pull Station, between elevator & West stairwell door
2-001-094 SA B2 E STAIRS PULL STN . MS . . Pull Station, by B-20 Room
2-001-095 SA B2 VACUUM CAGE . . . . HD . . West of elevator
2-001-096 SA B2 B-20 SERVICE ROOM . HD . . Room near East stairwell, door secured with OPS lock
TRI - between elevator & West stairwell door
2-001-097 SA B2 HEAT DETECT. (15)
- module monitoring the following 15 devices -
TRI-R - in MHESA room 34 on North wall
2-001-098 MHESA L1 CLEAN RM FAN SHUTDOWN . CO . . Fan shutdown relay for HVAC fan for MHESA L1 Clean Room
Note: Only activates if 2-001-034 MHESA L1 CLEAN RM DUCT SMOKE Detector goes into Alarm
TRI's - for the following five addresses : SAB3, north wall by boot box
2-001-100 SA B3 VAULT TUNNEL E
TRAILER Gg
CZM - at North West corner, near door Gg1
2-002-088 TRAILER Gg
- module monitoring the following 22 devices -
TRAILER Gg EXTENSION
CZM - North West corner of Trailer Gg, near door Gg1
2-002-089 TRAILER Gg EXTENSION
- module monitoring the following 14 devices -
2-002-095 TRAILER Gg EXT. ELR
VARIOUS
2-003-001 MHESA ALARM BELLS
2-003-002 TRAILER Gg AND EXT. BELLS
3-003-003 CA DOOR HOLDERS . . CO . . . Chemistry Annex door holders. Relay in CA XLS-3
2-003-006 M-8 BLDG. ALARM BELLS
SERVICE ANNEX also 2-001-027 to 2-001-039
STORES and DESIGN OFFICE FACILITY , XLS - 7
TRI-D for the following 2 addresses: - Mechanical room, #104
TRI-D for the following 2 addresses: - Mechanical room, #104
TRI-D for the following 2 addresses: - Mechanical room, #104
TRI-D for the following 2 addresses: - Mechanical room, #104
TRI-D for the following 2 addresses: - Mechanical room, #104
IMPORTANT INSTRUCTION: IF THIS SYSTEM IS ACTIVATED, IT MUST BE DRAINED AND RESET BY THE SPRINKLER SERVICE COMPANY.
See "Service Providers"
7-013-028 SDF CANOPY SPRINKLER VALVE . TS . . Canopy sprinklers shutoff valve = SUPERVISORY
TRI-S for the following address: - Mechanical room, #104
7-014-048 SDF LEVEL 1 AC DUCT SMOKE  . . SMK . Air Conditioner return duct smoke detector
CHEMISTRY ANNEX , XLS - 3
TRI-D for the following two addresses, In ceiling near door 26
TRI-D for the following two addresses, CA B1 Room 30 North wall West
TRI-D for the following two addresses, CA B1 Room 30 North wall East
TRI-S for the following address, CA B1 Room 30 North wall East
TRI-S for the following address, CA B1 Room 30 North wall East
3-019-022 CA G NORTH DOOR. . . . . . MS . . . Pull Station, door 11, North
TRI-D for the following two addresses, In west wall by door 100 (under plywood cover)
TRI-D for the following two addresses, In west wall by door 100 (under plywood cover)
3-019-028 CA G N. HALL DUMB WAITER . SMK I . .Ground Floor, North Hall, Dumb Waiter Shaft
TRI-D for the following two addresses, In North stairwell at ground floor eye level
TRI-D for the following two addresses, In ceiling near centre stairwell, South door
TRI-D for the following two addresses, In ceiling near room 227
TRI-D for the following two addresses, at ceiling level in North East corner, L2
MESON HALL
CHEMISTRY ANNEX - continued
CHEMISTRY ANNEX - continued
3-021-002 BELL CCT. CHEMISTRY ANX
4-027-001 RCA3 B2 ELEV Machine Rm. . . . SMK . . . Elevator Machine Room at bottom of stairwell
4-027-015 RCA3 B1 Top ELEV Shaft . . . . SMK . . . Top of Elevator Shaft, B1 level
MAIN OFFICE BUILDING , XLS - 1
Module for the following six addresses is located in the XLS-1 panel, MOB Lobby.
TRAILER Hh
1-036-004 TRAILER Hh BELLS . . . . . B . . North Hallway
1-037-001 MOB BELL CCT. SOUTH WING
TRI's - for the following 11 addresses: Water Supply Room, above door 8-041-015 ECOMP L1 SPRINKLER FLOW . . . . . . FS . . Sprinkler Flow switch for L1 level, North
8-041-017 ECOMP COMP RM SPRINK FLOW . . . . . FS . . Sprinkler Flow switch for Compressor Room
8-041-019 ECOMP G SPRINKLER FLOW . . . . . . . FS . . Sprinkler Flow switch for Ground floor North (washrooms & sprinkler room)
8-041-021 ECOMP CANOPY SPRINKLER FLOW . . . . FS . . Canopy sprinklers (over bike racks)
5-051-011 ISAC EXPHAL G TRILIS FAULT . xx . . . VESDA system, ISAC Experimental Hall Room 116. Monitoring room 112 (TRILIS):
- - - Note : See 5-051-011 and 5-051-012 for TRILIS VESDA Trouble and Supervisory signals - - -
5-052-060 ISAC EXPHAL FRANCIUM ROOM . . SMK . . . ISAC1 Experimental Hall, Francium Room, HVAC return duct
5-055-001 ISAC SPRKSOL #1 EXPHAL L1 . . SOL . . . Experimental Hall ground level South, room 116
5-055-002 ISAC SPRKSOL #2 TMB&IS RM . . SOL . . . TMB ground level, room 102 (area West of elevator)
5-055-003 ISAC SPRNKSOL #3 ION C.R. . . SOL . . . TMB B1 Lobby, above door 03
5-055-004 ISAC SPRNKSOL #4 RH MAINT . . SOL . . . TMB B1 Lobby, above door 04
ISAC II BUILDINGS , XLS - 6
6-061-001 ISAC2 G EXP.HALL SW EXIT . . MS . . Pull Station, Exp.Hall South West corner, West wall, North of Exit door to Stair #3
ACCELERATOR VAULT LINEAR BEAM DETECTORS
These three beams are in "series" to cover the entire length of the Accelerator Vault.
The following three beams are parallel, aiming South to North. ARIEL BUILDING , XLS - 9
9-091-015 ARIEL G N C.S.B. WEST DOOR . . . MS . . Pull Station at West door
PLANT SERVICES BUILDING , XLS - 12
TRIUMF - FIRE ALARM SYSTEM
SPRINKLER VALVES AND DEVICES
VARIOUS: Main Office Building, Hazardous Materials, MHESA, Remote Handling,
1-035-005 MOB G UNDER AUDITORIUM TS . . . . TS . Main valve, Glycol sprinklers under Auditorium - Supervisory
2-001-059 MHESA B1 RCR SPRNK FLOW . . FS . . Flow switch for RCR Lab sprinklers. Located in MHESA B1 room 03
TS Main Sprinkler Supply Valve Tamper switch , at door 100 , North , TROUBLE ONLY
FS - ALARM
FS - ALARM
CHEMISTRY ANNEX , XLS - 3
- In ceiling of B1 Lobby -
3-019-013 CA B1 CP42 PS RM SPRINK . . FS . . Sprinkler Water Flow in any of these areas :
B1 floor, CP42/TR30 Control Room
3-019-014 CA B1 CP42 PS RM SPKL TS . TS . . Tamper switch for 3-019-013 = SUPERVISORY
- In ceiling near door 26 -
3-019-015 CA B1 SPRINKLERS . . . . . FS . . B1 floor, Sprinklers Water Flow
- Near B1 North door -
3-019-017 CA B1 TR30 PS RM SPRINK . . FS . . TR30 P.S. room, Sprinklers Water Flow
- Near Main valves, B1 North -
- In ceiling by door 100 -
3-019-024 CA G N. SPRINKLERS . . . . FS . . Ground Floor North, Water Flow
- In ceiling by door 100 -
3-019-026 CA G S. SPRINKLERS . . . . FS . . Ground Floor South, Sprinkler Water Flow
- in North stairwell -
3-019-029 CA G LOAD BAY E. SPRINK . . FS . . East Loading Bay Sprinkler
- In ceiling near centre stairwell, South door -
3-019-031 CA L1 S. SPRINKLERS . . . . FS . . L1 Floor South Water Flow
- In ceiling near room 227 -
3-019-033 CA L1 N. SPRINKLERS . . . . FS . . L1 Floor North Water Flow
- at ceiling level in North East corner -
3-019-035 CA L2 N. SPRINKLERS . . . . FS . . North Penthouse Water Flow
3-019-045 CA B1 MAIN SPRNK VLV TS . . TS . . Tamper switch on the internal main sprinkler suppply valve = SUPERVISORY
3-020-032 CA L2 S. SPRINKLERS . . . . FS . . L2 South Penthouse, Sprinkler Water Flow
RCA3 BUILDING , XLS - 4
4-027-002 RCA3 B2 SPRINKLERS . . . . . FS . . sprinkler flow switch
4-027-008 RCA3 B1 SPRINKLERS . . . . . FS . . sprinkler flow switch
4-027-010 RCA3 B1 MAIN SPRINK VLV. . . TS . . main sprinkler valve tamper switch
4-027-011 RCA3 G SPRINKLERS . . . . . FS . . sprinkler flow switch
4-027-013 RCA3 L1 SPRINKLERS . . . . . FS . . sprinkler flow switch
4-028-014 RCA3 L2 SPRINKLERS . . . . . FS . . sprinkler flow switch
ISAC BUILDING , XLS - 5
5-051-016 ISAC EXPHAL G RCKRM L1 TS . TS . . Tamper Switch on sprinkler valve in room 116, Exp. Hall G South, which supplies L1, Low and High
energy Counting rooms = SUPERVISORY
5-051-017 ISAC EXPHAL S SPRINK FS . . . FS . . Room 113, Janitor. Flow Switch on sprinkler system which feeds the entire G and L1 centre block of rooms.
5-051-021 ISAC EXPHAL G,NE SPRNK FS . . FS . . Flow Switch, in ISAC Exp. Hall North East corner. For sprinkler heads above the main sprinkler valves.
5-051-023 ISAC EXPHAL MAIN SPRNK FS . . FS . . ISAC Exp. Hall North East Corner.
5-051-025 ISAC EXPHAL MAIN SPRNK TS . . TS . . ISAC Exp. Hall North East Corner.
5-051-029 ISAC TMB B2 LOBBY SPNK FS . . FS . . Flow Switch, Main sprinkler supply for TMB B2 floor areas: Stairwell, Lobby, rm 004 Safety Office, rm
006 Hot cells South, 010 Hot cells North. Switch located in the cabinet in the B2 Lobby area.
5-051-035 ISAC TMB B2 TRINAT SPK TS . . TS . . Tamper switch for sprinklers in room 012, TRINAT, Exp. Hall B1, Located in Active Service room, TMB
B2, near door 002 = SUPERVISORY
5-051-036 ISAC TMB B2 CNTL ZN SP TS . . TS . . Tamper switch for room 08 & 09, Target Hall Entrance area, room 13 Shower & room 14 Laundry.
Located in Active Service room, TMB B2 near door 002 = SUPERVISORY
5-051-038 ISAC TMB B1 LOBBY SPNK TS . . TS . . For room 03, TMB B1, Ion Source Control room, outside room 03 = SUPERVISORY
5-051-039 ISAC TMB B1 LOBBY SPNK TS . . TS . . For room 05, TMB B1, Remote Handling Control room, outside room 04 = SUPERVISORY
5-051-040 ISAC TMB B1 LOBBY SPNK FS . . FS . . Flow Switch in cabinet in TMB B1 Lobby 01 for sprinkler system supplying the Hallway, room 6 & room 7.
5-051-053 ISAC EXPHALL G N/E SPRNK . . CI . . . TRI - In ISAC Exp. Hall North East Corner.
5-052-018 ISAC TMB G MAT.BAY SPK TS . . TS . . For room 103, TMB G, Stable Ion Source room. Located in room 102, TMB ground (West of elevator) = SUPERVISORY
5-052-027 ISAC TMB G MAT.BAY SPK FS . . FS . . In cabinet in room 102 (area West of lobby). Supplies TMB Ground level, except for room 103 Stable Ion Source room.
5-052-037 ISAC TMB PENTHOUSE SPK FS . . FS . . Penthouse, TMB L2, all areas, in P.H. South of P3
5-052-048 ISAC TMB L1 DESOFF SPK FS . . FS . . Design Office, All Areas, in TMB L1 Lobby cabinet
5-055-001 ISAC SPRKSOL #1 EXPHAL L1 . . SOL . . For Exp Hall level L1, Low and High Energy counting rooms. Located in room 116, Exp. Hall G, South.
5-055-002 ISAC SPRKSOL #2 TMB&IS RM . . SOL . . For room 103, TMB G, Stable Ion Source room. Located in room 102, TMB Ground (West of elevator).
5-056-001 ISAC SPRNK SOL #5 TMB . . . . SOL . . Main sprinkler supply for TMB B2 floor areas:
Stairwell, Lobby, rm 004 Safety Office, rm 006 Hot cells South, 010 Hot cells North. Located in TMB B2
Lobby. Large solenoid valve at ceiling level.
5-058-001 ISAC SPRNK SOL #7 TRINAT . . SOL . . For room 012, TRINAT Exp. Hall B1, Located in Active Service room, TMB B2, near door 002.
5-058-002 ISAC SPRNKSOL #6 THCNTLZN . . SOL . . For room 08 & 09, Target Hall Entrance area, room 13 Shower & room 14 Laundry. Located in Active
Service room, TMB B2 near door 002.
5-059-001 ISAC SPRNKSOL #3 ION C.R. . . SOL . . For room 03, TMB B1, Ion Source Control room, Outside room 03.
5-059-002 ISAC SPRNKSOL #4 RH MAINT . . SOL . . For room 05, TMB B1, Remote Handling Control room, outside room 04.
ISAC II BUILDING , XLS - 6
6-061-060 ISAC2 G AUX P.S. AC LOSS . . CI . . Pre-action solenoid power supply. Power loss.
TRI-S Inside XLS-6 . . = SUPERVISORY
6-062-005 ISAC2 G RF/CRYO/EL SPRNK . . FS . . Exp. Hall NE, Pre-action system for R.F., Cryogenics and Elec. rms (# 163, 164, 165)
6-062-007 ISAC2 G RF/CRYO/EL L.AIR . . CI . . Exp. Hall NE, Low Air pressure signal for 062-005 = SUPERVISORY
6-062-008 ISAC2 L1 PS/COMP LOW AIR . . CI . . Exp. Hall NE, Low Air pressure signal for 062-009 = SUPERVISORY
6-062-009 ISAC2 L1 PS/COMP SPRINK . . . FS . . Exp. Hall NE, Pre-action system for L1 (Power supply & Computer rms - #260 & #242)
6-062-011 ISAC2 G VLT/LABS SPRINK . . . FS . . Exp. Hall NW, piping second from top
6-062-014 ISAC2 G EXP HALL SPRINK . . . FS . . Exp. Hall NE, in corner 16 feet above floor
6-062-016 ISAC2 G BKFLOW PREV TS1 . . . TS . . Exp. Hall NE, Valve on upstream side of backflow preventer = SUPERVISORY
6-062-019 ISAC2 G OFFICES SPRINK . . . FS . . Exp. Hall NW, piping third from top
6-062-021 ISAC2 L1 OFFICES SPRINK . . . FS . . Exp. Hall NW, Top piping
6-062-023 ISAC2 L2 SPRINKLERS . . . . . FS . . Exp. Hall NW, Bottom piping
6-067-001 ISAC2 G RF/CRYO/EL SOL. . . . CO . . pre-action solenoid from XLS-6, Trouble only
SDF BUILDING , XLS - 7
7-013-019 SDF G MAIN SPRNK SUP TS #1 . . TS . . Main water supply to building shutoff valve = SUPERVISORY
7-013-021 SDF GRND BACKFLOW VALVE #1 . . TS . . Backflow preventer valve #1 = SUPERVISORY
7-013-023 SDF G FLOOR SPRINKLER FLOW . . FS . . Ground floor Sprinkler Flow Switch
7-013-025 SDF LEVEL 1 SPRINKLER FLOW . . FS . . L1 floor Sprinkler Flow Switch
7-013-027 SDF CANOPY SPRNK FLOW . . . . FS . . Canopy sprinklers Flow Switch
7-013-029 SDF CANOPY SPRINKLER LOW AIR . CI . . Low Air pressure signal for 013-027 dry sprinkler system = SUPERVISORY
COMPRESSOR BUILDING , XLS - 8
8-041-015 ECOMP 2ND FL SPRINKLER FLOW . . FS . . Sprinkler Flow switch for L1 level
8-041-017 ECOMP COMP RM SPRINK FLOW . . . FS . . Sprinkler Flow switch for Compressor Room
8-041-019 ECOMP G SPRINKLER FLOW . . . . . FS . . Sprinkler Flow switch for Ground floor level
8-041-021 ECOMP CANOPY SPRINKLER FLOW . . FS . . Canopy sprinklers over bike racks
8-041-024 ECOMP SPRK BCKFLOW VALVE1&2 . . TS . . Tamper switches on either valve = SUPERVISORY
ARIEL BUILDING , XLS - 9
TRI - for the following two addresses is located in the North Service Shaft, B1 Level. Access from stairwell
TRI - for the following two addresses is located in the North Service Shaft, G Level. Access from stairwell
TRI - for the following two addresses is located in the North Service Shaft, G Level. Access from stairwell
TRI - for the following address is located in the B2 Mechanical Room, on ceiling above the valve
TRI - for the following two addresses is located on the B2 North level. Access from foot of stairwell
TRIs - for the following three addresses are located by the Main Sprinkler Supply Valve & B.F.P.'s, L2 North
TRI - for the following two addresses is located by the Main Sprinkler Supply Valve & B.F.P.'s, L2 North
TRI - for the following two addresses is located on L2 adjacent to the south stairwell door
9-093-038 ARIEL PAINT BOOTH LG_L2 TAMPER . TS . . Tamper Switch for 093-037 FS = SUPERVISORY
TRI - for the following two addresses is located on the B2 Level, in the South stairwell
TRI - for the following two addresses is located in a wall hatch, accessed from the south stairwell
TRI - for the following two addresses is located in the south service shaft, G Level, access from stairwell
TRI - for the following two addresses is located in the south service shaft, L1 level, access from stairwell
TRIUMF - FIRE ALARM SYSTEM
ELEVATING DEVICES DETECTORS
1-035-044 MOB L1 ELEV TOP OF SHAFT . . SMK P . . L1 Floor, Top of Elevator Shaft
2-001-006 MHESA L1 TOP ELEV. SHAFT . . SMK I . . Top of Elevator Shaft
2-001-014 M-8 G ELEVATOR SHAFT . . . . SMK I . . Top of Elevator Shaft, L1, visible with car at ground floor
2-001-054 SA B3 ELEVATOR PIT . . . . . HD . . . .In pit below Elevator on South wall (below doorway)
2-001-058 SA L2 ELEVATOR SHAFT TOP . . SMK I . . Top of Elevator Shaft
3-019-028 CA G N. HALL DUMB WAITER . . SMK I . . Ground Floor, North Hall, Dumb Waiter Shaft
3-020-020 CA G Rm 103 DUMB WAITER . . SMK P . . Ground Floor, Room 103 top of Dumb Waiter Shaft
3-020-024 CA L2 TOP OF ELEV. SHAFT . . SMK I . . L2 level, Top of Elevator Shaft
4-027-001 RCA3 B2 ELEV Machine Rm. . . SMK . . . Elevator Machine Room at bottom of stairwell
4-027-015 RCA3 B1 Top ELEV Shaft . . . SMK . . . Top of Elevator Shaft, B1 level
5-051-052 ISAC TMB L1 TOP ELEV SHFT. . SMK I . . Top of Elevator Shaft
6-063-012 ISAC2 L1 TOP ELEV. SHAFT . . SMK I . . Top of Elevator Shaft
9-092-010 ARIEL B2 N ELEVATOR PIT . . . HD . . Heat Detector in North Elevator Pit
9-092-011 ARIEL N ELEVATOR TOP . . . . SMK . . Smoke Detector at the top of the North Elevator shaft
9-093-019 ARIEL L2 S ELEV SHAFT TOP . . SMK . . Smoke Detector at the top of the South Elevator shaft
9-094-017 ARIEL B2 S ELEV. PIT HD . . . HD . . . Heat Detector in South Elevator Pit
2-007-001 SA L1 E STAIRS PULL STN . MS . . . Pull Station, at top of East stairs
2-007-002 SA L1 W STAIRS PULL STN . MS . . . Pull Station, at top of West stairs
2-007-003 SA L1 TOP OF E STAIRS . . SMK . . Top of East stairwell
2-007-004 SA L2 TOP OF W STAIRS . . SMK . . Top of West stairwell
2-007-005 SA L2 ELEV MACHINE RM . . SMK . . Inside Elevator Machine room
2-007-006 SA L1 FAN RM SE . . . . . HD . . . Ceiling of Fan Room, S E, above green compressor
2-007-007 SA L1 FAN RM N CENTRE . . HD . . . Ceiling of Fan Room, North Centre
2-007-008 SA L1 FAN RM SW . . . . . HD . . . Ceiling of Fan Room, S W, hidden above ME140 duct
2-007-009 SA L1 VAULT FAN ROOM. . . HD . . . Ceiling of Vault Exhaust Fans Room
2-007-010 SA L1 BOILER ROOM E . . . HD . . . Above East Boiler
2-007-011 SA L1 BOILER ROOM W . . . HD . . . Above West Boiler
2-007-012 SA L1 HALL EAST . . . . . SMK . . just inside ISIS area
2-007-013 SA L1 HALL CENTRE . . . . SMK . . near Fan Room East double doors
2-007-014 SA L1 HALL WEST . . . . . SMK . . between Fan Room Centre and West double doors
2-007-015 SA L1 LOADING BAY . . . . SMK . . Open area accessible to 10T crane
2-007-016 SA L1 I1 SERVICE RM . . . SMK . . Enter through Boiler Room
2-007-017 SA L1 ISIS I1 CONSOLE . . HD . . . above I3/4 console
2-007-018 SA L1 ISIS I3/4 CONSOLE . SMK . . above I1 console at rack CON 20
2-007-019 SA L1 ISIS WORK AREA. . . SMK . . above fume hoods
2-007-020 SA L1 ISIS I3/4 HALL SE . HD . . . South Centre of ISIS extension, in machining area
2-007-021 SA L1 ISIS I3/4 HALL SW . HD . . . South West corner of ISIS extension
TRI - on south west corner of I2 enclosure
2-007-022^1 SA L1 ION SOURCE 1 ROOM
HD . . . Heat detector on ceiling of Ion Source 1 room
TRI - on south west corner of I2 enclosure
2-007-022^2 SA L1 ION SOURCE 2 ROOM HD . . . Heat detector on ceiling of Ion Source 2 room
TRI - mezzanine level, west of beamline, north of I3/4 room
2-007-024 SA L2 ION SRC 3/4 ROOM HD . . . Heat detector on ceiling of Ion Source 3/4 room
2-007-025 SA L2 I3/4 LASER ROOM . . HD . . . Inside Laser Room
2-007-026 SA L2 LASER RM PULL STN . MS . . . Pull Station, outside Laser Room door
2-007-027 SA L2 ISIS MEZZ NORTH . . SMK. . . ISIS Mezzanine by I1
2-007-028 SA L2 ISIS MEZZ SOUTH . . SMK. . . ISIS Mezzanine by top of stairs
2-007-029 SA L2 ISIS MEZZ PULL STN. MS . . . Pull Station, at top of stairs
2-007-030 SA L1 ISIS XFMR VLT TOP . HD . . . Overtop 300KV Isolation transformers Vault
2-007-031 SA L2 LASER RM HVAC MEZZ. HD . . . Up ladder to HVAC mezzanine, 10 feet West, on South wall of I3/4 enclosure, facing South
2-007-032 SA L1 FAN ROOM ABOVE T1 . SMK. . . West end of Fan Room above transformer T1
2-007-034 SAE L1 RM 207 CEILING . . SMK
2-007-035 SAE L1 RM 207 FLR NORTH . SMK. . . underfloor detector
2-007-036 SAE L1 RM 207 FLR SOUTH . SMK. . . underfloor detector
2-007-037 SAE L1 RM 208 CEILING . . SMK
2-007-038 SAE L1 RM 208 FLR NORTH . SMK. . . underfloor detector
2-007-039 SAE L1 RM 208 FLR SOUTH . SMK. . . underfloor detector
2-007-040 SAE L1 RM 209 CEILING . . SMK
2-007-041 SAE L1 RM 209 FLR NORTH . SMK. . . underfloor detector
2-007-042 SAE L1 RM 209 FLR SOUTH . SMK. . . underfloor detector
2-007-043 SAE L1 RM 210 CEILING . . SMK
2-007-044 SAE L1 RM 210 FLR NORTH . SMK. . . underfloor detector
2-007-045 SAE L1 RM 210 FLR SOUTH . SMK. . . underfloor detector
2-007-046 SAE L1 RM 211 CEILING . . SMK
2-007-047 SAE L1 RM 212 CEILING . . SMK
2-007-048 SAE L1 RM 212 FLR NORTH . SMK. . . underfloor detector
2-007-049 SAE L1 RM 212 FLR SOUTH . SMK. . . underfloor detector
2-007-050 SAE L1 HALL EAST END . . .SMK. . . near Room 217
2-007-051 SAE L1 HALL EAST CENTRE . SMK. . . near Room 219
2-007-052 SAE L1 HALL WEST CENTRE . SMK. . . near Room 221
2-007-053 SAE L1 HALL E PULL STN. . MS . . . Pull Station, on North wall, near East double doors
2-007-054 SA L1 VLT EXH.DUCT NORTH. DS . . . Vault Exhaust Fan Room, enter via door 203,
on North fan exhaust duct, 6' above floor, faces East
2-007-055 SA L1 VLT EXH.DUCT SOUTH. DS . . . Vault Exhaust Fan Room, enter via door 203,
on South fan exhaust duct, 6' above floor, faces East
2-007-056 SA L1 ME-140 RETURN DUCT. DS . . . Fan Room, enter via door 205 Centre, on East side of return duct, South of fan housing, 7' above floor, faces East
2-007-057 SA L1 ME-140 RET. DUCT N. DS . . . Fan Room, enter via door 205 East, on duct immediately to East, 6' above floor, faces South
2-007-058 SA L1 ME-141 SUPPLY DUCT. DS . . . Fan Room, enter via door 205 East, on duct above fluorescent light just East of fan housing, 10' above floor, faces South
2-007-059 SA L1 ME-141 RETURN DUCT. DS . . . Fan Room, enter via door 205 East, on duct above ME-141 compressor (grey), 10' above floor, faces North
2-007-060 SAE L1 HALL WEST END. . . SMK . . . near Room 224
2-008-010 DRILL SWITCH ACTIVATED. . CI . . . DRILL SWITCH in rear of Rack "A" in Main Control Room. ACTIVATES ALL BELLS ON SITE
2-008-012 SA G CR CEILING NE . . . SMK . . Main Control Room
2-008-013 SA G CR CEILING NW . . . SMK . . Main Control Room
2-008-014 SA G CR CEILING SE . . . SMK . . Main Control Room
2-008-015 SA G CR CEILING SW . . . SMK . . Main Control Room
2-008-016 SA G CR UNDERFLOOR NE . . SMK . . Main Control Room
2-008-017 SA G CR UNDERFLOOR NW . . SMK . . Main Control Room
2-008-018 SA G CR UNDERFLOOR SE . . SMK . . Main Control Room
2-008-019 SA G CR UNDERFLOOR SW . . SMK . . Main Control Room
2-008-020 SA G COMP RM CEILING NE . SMK . . Computer Room next to Control Room
2-008-021 SA G COMP RM CEILING NW . SMK . . Computer Room next to Control Room
2-008-022 SA G COMP RM CEILING SE . SMK . . Computer Room next to Control Room
2-008-023 SA G COMP RM CEILING SW . SMK . . Computer Room next to Control Room
2-008-024 SA G COMP RM FLOOR NE . . SMK . . Computer Room next to Control Room
2-008-025 SA G COMP RM FLOOR NW . . SMK . . Computer Room next to Control Room
2-008-026 SA G COMP RM FLOOR SE . . SMK . . Computer Room next to Control Room
2-008-027 SA G COMP RM FLOOR SW . . SMK . . Computer Room next to Control Room
2-008-028 SA G PROG RM CEILING N . SMK . . Programming Room, East end of Hall
2-008-029 SA G PROG RM CEILING S . SMK . . Programming Room, East end of Hall
2-008-030 SA G PROG RM FLOOR N . . SMK . . Programming Room, East end of Hall
2-008-031 SA G PROG RM FLOOR S . . SMK . . Programming Room, East end of Hall
2-008-032 SA G SOUTH HALL EAST . . SMK . . Near Safety Office, room 105
2-008-033 SA G SOUTH HALL CENTRE . SMK . . Near Controls Office, room 106
2-008-034 SA G SOUTH HALL WEST . . SMK . . Outside Lunchroom, room 108
2-008-035 SA G NORTH HALL EAST . . SMK . . Near room 113
2-008-036 SA G NORTH HALL WEST . . SMK . . Near Elevator
2-008-037 SA G HALL EAST PULL STN . MS . . . Pull Station, door 104, East stairwell
2-008-038 SA G HALL WEST PULL STN . MS . . . Pull Station, door 1, double doors near Lunchroom
2-008-039 SA G HALL NORTH PULL STN. MS . . . Pull Station, door 114, West stairwell (elevator)
2-008-040 SA G ROOM 108, LUNCH . . HD . . . Lunchroom
2-008-041 SA G ROOM 109, MENS . . . HD . . . Mens Washroom
2-008-042 SA G ROOM 110, LADIES . . HD . . . Ladies Washroom
2-008-043 SA G ROOM 111, SHOWER . . HD . . . Ladies Shower room
2-008-044 SA G ROOM 112, JANITOR . HD . . . Janitor room
2-008-045 SA G ROOM 116, FIRST-AID SMK . . First-Aid room
2-008-046 SA G ROOM 117, N.DECON . SMK . . Personnel Decontamination Room
2-008-047 SA G ROOM 118, S.DECON . HD . . . Materials Decontamination Room
2-008-048 SA G LOADING BAY EAST . . SMK . . Service Annex Loading Bay, near East double doors
2-008-049 SA G LOADING BAY WEST . . SMK . . Service Annex Loading Bay, near West roll-up door
2-008-050 SA G DECON HALL S WALL . SMK . . On "I" beam, South of room 118 South wall
2-008-051 SA G DECON HALL CENTRE . SMK . . On ceiling between Decontamination rooms 117 and 118
2-008-052 SA G DECON HALL S P.S. . MS . . . Pull Station, door 21, on column South of double doors, across from Rm 118
2-008-053 SA P-HALL ROOF STAIRS PS. MS . . . Pull Station, at top of Proton Hall Roof stairs from SA Loading Bay, on column to the East
7-013-001 SDF G FLR NORTH STAIR EXIT . . MS . . Pull Station, at foot of north east stairs
7-013-002 SDF G FLR NORTH LOBBY EXIT . . MS . . Pull Station, in North Lobby near Fire Panel
7-013-003 SDF G FLR EAST @ DBL DR 106A . MS . . Pull Station, at east side double doors
7-013-004 SDF GRND FLR EAST ENTRANCE . MS . . Pull Station, at east entrance door
7-013-005 SDF GRND FLR SOUTH ENTRANCE . MS . . Pull Station, at south entrance door
7-013-006 SDF G FLR WEST LOADING DOCK . MS . . Pull Station, at door on loading dock
7-013-007 SDF G FLR WEST EMERG EXIT DR . MS . . Pull Station, at west side emergency exit door
7-013-008 SDF G FLR WEST MECH RM 104 . . MS . . Pull Station, at Mechanical room door
7-013-019 SDF G MAIN SPRNK SUP TS #1 . . TS . . Main water supply to building shutoff valve = SUPERVISORY
7-013-020 SDF G MAIN SPRNK SUP TS #2 . . TS . . Main Sprinkler supply shutoff valve = SUPERVISORY
7-013-021 SDF GRND BACKFLOW VALVE #1 . . TS . . Backflow preventer valve #1 = SUPERVISORY
7-013-022 SDF GRND BACKFLOW VALVE #2 . . TS . . Backflow preventer valve #2 = SUPERVISORY
7-013-023 SDF G FLOOR SPRINKLER FLOW . . FS . . Ground floor Sprinkler Flow Switch
CI . . Switch cover off = TROUBLE
7-013-024 SDF G FLOOR SPRINKLER VALVE . TS . . Ground floor sprinklers shutoff valve (for 013-023) = SUPERVISORY
7-013-025 SDF LEVEL 1 SPRINKLER FLOW . . FS . . L1 floor Sprinkler Flow Switch
CI . . Switch cover off = TROUBLE
7-013-026 SDF LEVEL 1 SPRINKLER VALVE . TS . . Level 1 floor sprinklers shutoff valve (for 013-025) = SUPERVISORY
7-013-027 SDF CANOPY SPRNK FLOW . . . . FS . . Canopy sprinklers Flow Switch. This is a DRY sprinkler system
CI . . Switch cover off = TROUBLE
Flow Switch located in room #104
7-013-029 SDF CANOPY SPRINKLER LOW AIR . CI . . Low Air pressure signal for 013-027 dry sprinkler system = SUPERVISORY
7-014-040 SDF LEVEL 1 TOP OF NTH STAIR . SMK . Top of north stairs
7-014-041 SDF LEVEL 1 NORTH STAIR EXIT . MS . . Pull Station at L1 door to north stairwell
7-014-044 SDF LEVEL 1 TOP OF STH STAIR . SMK . Top of south stairs
7-014-045 SDF LEVEL 1 SOUTH STAIR EXIT . MS . . Pull Station at L1 door to south stairwell
CO . . Air Conditioner fan shutdown
7-015-001 SDF Ground Floor Bells
7-015-002 SDF Level 1 Bells
7-015-003 SDF Ground Floor Strobe Circuit
7-015-004 SDF Level 1 Strobe Circuit
3-019-001 CA B1 CENTRE STAIRS (N) . MS . . . Pull Station, B1 floor, Hot cell area hall, North of Centre stairs
3-019-002 CA B1 NORTH STAIRS . . . . MS . . . Pull Station, B1 floor, Hot cell area hall, at North Stairs
3-019-003 CA B1 NORTH-EAST STAIRS . MS . . . Pull Station, B1 floor, TR30 power supply area, at North Stairs
3-019-004 CA G HALL C STAIRS (N) . . MS . . . Pull Station, Ground Floor, North hall at Centre stairs
3-019-006 CA G NORTH BY N. STAIRS . MS . . . Pull Station, door 10, North end of hall by Stairs, North East door
3-019-007 CA G SHIP RM. EAST DOORS . MS . . . Pull Station, door 84, East door, Shipping
3-019-008 CA L1 HALL C STAIRS(N) . . MS . . . Pull Station, L1 Floor, South Centre Hall
3-019-009 CA L1 HALL C STAIRS(N) . . MS . . . Pull Station, L1 Floor Hall, at Centre Stairs, near room 217
3-019-010 CA L1 NORTH STAIRS . . . .MS . . . Pull Station, L1 Floor Hall, at North Stairs
3-019-011 CA L2 BY NORTH STAIRS . . MS . . . Pull Station, L2, North Penthouse by North Stairs
3-019-012 CA L2 BY SOUTH DOOR . . . MS . . . Pull Station, L2, North Penthouse by South door
3-019-013^1 CA B1 CP42 PS RM SPRINK. . FS . . Sprinkler Water Flow in any of these areas :
B1 floor: CP42/TR30 old Control Room , Room 14 (CP42 Power Supply room) , Room 24 (service room)
3-019-013^2 CA B1 CP42 PS RM SPKL TS . TS . . Tamper switch for 3-019-013^1 = SUPERVISORY
3-019-014^1 CA B1 SPRINKLERS . . . . . FS . . . B1 floor, Sprinklers Water Flow
3-019-014^2 CA B1 SPKLR TAMPER . . . . TS . . . Tamper switch for 3-019-014^1 = SUPERVISORY
3-019-015^1 CA B1 TR30 PS RM SPRINK . FS . . . TR30 P.S. room, Sprinklers Water Flow
3-019-015^2 CA B1 TR30 PS RM SPKL TS . TS . . . Tamper switch for 3-019-017 = SUPERVISORY
<
3-019-016^1 CA G LOAD BAY W. SPRINK . . FS . . West Loading Bay, Sprinkler Water Flow
3-019-016^2 CA G LOAD BAY W. SPKLR TS . TS . . Tamper switch for 3-019-019 = SUPERVISORY
3-019-021 CA B1 MAIN SPRINK.SUPPLY . FS . . . Main Sprinkler Supply Flow Switch (30 sec delay) = ALARM
3-019-023 CA B1 MAIN SPRINK TAMPER . TS . . . Main Sprinkler Supply Valve Tamper Switch (for 3-019-021) = SUPERVISORY
3-019-018^1 CA G N. SPRINKLERS . . . . FS . . . Ground Floor North, Water Flow
3-019-018^2 CA G N. SPKLR TAMPER . . . TS . . . Tamper switch for 3-019-024 = SUPERVISORY
3-019-019^1 CA G S. SPRINKLERS . . . . FS . . . Ground Floor South, Sprinkler Water Flow
3-019-019^2 CA G S. SPKLR TAMPER . . . TS . . . Tamper switch for 3-019-026 = SUPERVISORY
3-019-020^1 CA G LOAD BAY SPRINKLERS . FS . . . CA Loading Bay, Sprinkler Water Flow
3-019-020^2 CA G LOAD BAY SPRINK TS . TS . . . Tamper switch for 3-019-029 = SUPERVISORY
3-019-024^1 CA L1 S. SPRINKLERS . . . .FS . . . L1 Floor South Water Flow
3-019-024^2 CA L1 S. SPKLR TAMPER . . .TS . . . Tamper switch for 3-019-031 = SUPERVISORY
3-019-025^1 CA L1 N. SPRINKLERS . . . FS . . . L1 Floor North Water Flow
3-019-025^2 CA L1 FLR N. SPKLR TS . . TS . . . Tamper switch for 3-019-033 = SUPERVISORY
3-019-026^1 CA L2 N. SPRINKLERS . . . FS . . . North Penthouse Water Flow
3-019-026^2 CA L2 N. SPRINKLR TAMPER . TS . . . Tamper switch for 3-019-035 = SUPERVISORY
3-019-037 CA G ELEC. RM LOAD BAY E . . SMK . . Electrical Room, door 86, outside, access from East Loading Bay
3-019-038 CA G CA WARM STORAGE BLD . . SMK . . Warm Storage Building, Outside East of berm
3-019-039 CA L2 TOP OF NORTH STAIR . . SMK . . Top of North stairs
3-019-040 CA L2 N. AHU-4 SUPPLY . . . DS . . . North Penthouse AHU-4 Supply
3-019-041 CA L2 N. AHU-5 RETURN . . . DS . . . North Penthouse AHU-5 Return, near South door
3-019-042 CA L2 N. AHU-3 . . . . . . . DS . . . North Penthouse AHU-3
3-019-043 CA L2 N. AHU-2 . . . . . . . DS . . . North Penthouse AHU-2
3-019-044 CA L2 N. AHU-1 . . . . . . . DS . . . North Penthouse AHU-1
TRI-D for the following two addresses, CA B1 Room 30 North wall East
3-019-045^1 CA B1 MAIN SPRNK VLV TS . TS . . . Tamper switch on the internal main sprinkler suppply valve = SUPERVISORY
3-019-045^2 CA B1 MAIN BFP VLVS TS . . TS . . . Two tamper switches on the back-flow preventer service valves = SUPERVISORY
3-020-001 CA B1 CONTROL ROOM . . . . . MS . . . Pull Station, CP42/TR30 Control Room
3-020-002 CA B1 HALL SOUTH . . . . . . MS . . . Pull Station, B1 floor, Hot cell area hall, at South Stairs, near room 001
3-020-003 CA B1 HALL CENTRE. . . . . . MS . . . Pull Station, B1 floor, Hot cell area hall, South of Centre stairs
3-020-004 CA G HALL CENTRE (S) . . . . MS . . . Pull Station, Ground floor, South hall, North end
3-020-005 CA G HALL SOUTH . . . . . . MS . . . Pull Station, Ground floor, South hall, South of centre stairs
3-020-006 CA L1 HALL CENTRE STAIRS . . MS . . . Pull Station, L1 floor hall, Centre stairs
3-020-007 CA L1 HALL SOUTH STAIRS . . MS . . . Pull Station, L1 floor hall, South stairs
3-020-008 CA L2 S PULL STNS/HEAT . . . MS . . . Pull Station, L2 floor, South Penthouse at South stairs
3-020-009 CA L2 S PULL STNS/HEAT . . . HD . . . South Penthouse, North
3-020-010 CA L2 S PULL STNS/HEAT . . . HD . . . South Penthouse, North East
3-020-038 CA L2 S PULL STNS/HEAT . . . HD . . . South Penthouse, South
3-020-039 CA L2 S PULL STNS/HEAT . . . HD . . . South Penthouse, South West
CZM - at B1 door to Chemistry Annex
3-020-009 MH B1 MEZZ & COUNT. RMS
- module monitoring the following 20 devices -
CZM - at B2 door to Chemistry Annex
3-020-010 MH B2 FLOOR & COUNT. RMS
- module monitoring the following 21 devices -
3-020-011 CA G S. RM 104, JANITOR . . HD . . Ground Floor South, room 104
3-020-012 CA G S. RM 102, JANITOR . . HD . . Ground Floor South, room 102
3-020-013 CA B2 ELEVATOR MACH. RM . . HD . . Elevator Machine room, MESON Hall B2 North East
3-020-014 CA B1 HALL CENTRE (S) . . . SMK . . Basement Hall, North
3-020-015 CA B1 HALL SOUTH . . . . . SMK . . Basement Hall, South
3-020-016 MH G NORTH SPIRAL STAIRS. . SMK . . Top of Spiral stairwell, MESON Hall, North West
3-020-017 CA G HALL CENTRE (S). . . . SMK . . Ground Floor Hall, Centre
3-020-018 CA G HALL SOUTH . . . . . . SMK . . Ground Floor Hall, South
3-020-019 CA G S.W. HALL . . . . . . SMK . . Ground Floor, South West Hall, near door 12
3-020-020 CA G Rm 103 DUMB WAITER . . SMK . . Ground Floor, Room 103 top of Dumb Waiter Shaft
3-020-021 CA L1 TOP CENTRE STAIRS . . SMK . . L1 Floor, Top of centre stairs
3-020-022 CA L1 HALL CENTRE (S) . . . SMK . . L1 Floor, North Hall at centre stairs
3-020-023 CA L1 HALL SOUTH . . . . . SMK . . L1 Floor, South Hall
3-020-024 CA L1 TOP OF ELEV. SHAFT . SMK . . L1 level, Top of Elevator Shaft
3-020-025 CA L2 TOP OF SOUTH STAIR . SMK . . L2 Floor, Top of South stairs
3-020-026 CA L2 S. AH-1 SUPPLY . . . DS . . L2 South Penthouse, AH-1 Supply
3-020-027 CA L2 S. AH-2 RETURN. . . . DS . . L2 South Penthouse, AH-2 Return
3-020-028 CA L2 S. AH-3 SUPPLY. . . . DS . . L2 South Penthouse, AH-3 Supply
3-020-029 CA L2 S. AH-4 RETURN. . . . DS . . L2 South Penthouse, AH-4 Return
3-020-031 CA L2 S. CF-1 . . . . . . . DS . . L2 South Penthouse, CF-1
TRI - for the following two addresses, near North door and AHU-4
3-020-032^1 CA L2 S. SPRINKLERS . . . FS . . . . L2 South Penthouse, Sprinkler Water Flow
3-020-032^2 CA L2 S. SPKLR TAMPER . . TS . . . . Tamper switch for 3-020-032 = SUPERVISORY
MESON HALL
CZM - at door 13, North West
3-020-034 MH G PULL STNS OR SMOKE
- module monitoring the following 9 devices -
CZM - at door 13, North West
3-020-035 MH G ABOVE MCC H,J,K,N
- module monitoring the following 4 devices -
TRI - at door 13, North West
3-020-036 MESON HALL GAS SHACK . . . . . . MS . . Pull Station at door
3-020-037 MESON HALL GAS SHACK . . . . . . HD . . Heat Detector on ceiling at centre of room
3-020-037 MH B2 COUNTING OFFICE 006 . . . SMK . .Meson Hall B2 East counting room
3-020-038 MH B2 COMPUTER ROOM 018 EAST . . SMK . .Meson Hall B2 Centre computer room, East side
3-020-039 MH B2 COMPUTER ROOM 018 WEST . . SMK . .Meson Hall B2 Centre computer room, West side
3-020-040 MH B2 COUNTING OFFICE 007 . . . SMK . .Meson Hall B2 West counting room
3-021-001 BELL CCT. MESON HALL N.
NOTE : all "LED"s are on Graphics Panel, CA G South West at door # 12
3-023-001 . L2 SOUTH WING LED
3-023-002 . L2 SOUTH SPRINKLER LED
3-023-003 . L2 NORTH SPRINKLER LED
3-023-004 . L2 NORTH WING LED
3-023-005 . G SOUTH WING LED
3-023-006 . G SOUTH SPRINKLER LED
3-023-007 . G NORTH SPRINKLER LED
3-023-008 . G NORTH WING LED
3-023-009 . G DUMB WAITER LED
3-023-010 . G W LOAD BAY SPRINK LED
3-023-011 . G ELECTRICAL ROOM LED
3-023-012 . G STORAGE BUILDING LED
3-023-013 . L2 SOUTH LED
3-023-014 . AHU-D LED
3-023-015 . AHU-C LED
3-023-016 . AHU-B LED
3-023-017 . AHU-A LED
3-023-018 . L2 SOUTH SPRINKLER LED
3-023-019 . AHU-4 LED
3-023-020 . AHU-3 LED
3-023-021 . AHU-2 LED
3-023-022 . AHU-1 LED
3-023-023 . L2 NORTH PENTHOUSE LED
3-023-024 . L2 NORTH SPRINKLER LED
3-023-025 . L1 NORTH STAIRS LED
3-023-026 . B1 SOUTH WING LED
3-023-027 . B1 SOUTH SPRINKLER LED
3-023-028 . B1 NORTH SPRINKLER LED
3-023-029 . B1 NORTH WING LED
3-023-030 . CYCLOTRON SPRINKLER LED
3-023-031 . G E LOAD BAY SPRINK LED
3-023-032 . FIRE DEPARTMENT LED
3-023-033 . TAMPER TBLE LED >
3-023-035 . TOP OF ELEVATOR SHAFT LED
3-023-036 . SOUTH STAIRS LED
3-023-037 . B1 CONTROL RM LED
3-023-038 . MESON HALL NORTH WING B2 LED
3-023-039 . MESON HALL NORTH WING B1 LED
3-023-040 . WEST ESCAPE STAIRS LED
3-023-041 . CENTRAL STAIRS LED
RCA3 BUILDING , XLS - 4
4-026-001 RCA3 BELL CIRCUIT . . . . . B . . . . B1 & B2 Floors
4-026-002 RCA3 BELL CIRCUIT . . . . . B . . . . Ground, L1 & L2 Floors
TRI - for the following two addresses is located on the south wall of the B2 floor, 7' east of the door
4-027-002 RCA3 B2 SPRINKLERS . . . . . . FS . . . . Sprinklers flow switch for B2 floor
4-027-003 RCA3 B2 SPRINKLER TAMPER . . . TS . . . . Tamper switch on 027-002 valve = SUPERVISORY
4-027-004 RCA3 B2 EXIT TO STAIRS . . . . MS . . . . Pull station, at door to stairs
4-027-005 RCA3 B1 EXIT TO CA HALWY . . . MS . . . . Pull station,
4-027-006 RCA3 B1 EXIT TO CA TR-30 . . . MS . . . . Pull station, at door to the TR-30 Power Supply room
4-027-007 RCA3 B1 EXIT TO STAIRS . . . . MS . . . . Pull station, at door to stairs
TRI - for the following two addresses is located on the cable tray 8' north & 6' west of door
4-027-008 RCA3 B1 SPRINKLERS . . . . . . FS . . . . Sprinklers flow switch for B1 floor
4-027-009 RCA3 B1 SPRINKLER TAMPER . . . TS . . . . Tamper switch on 027-008 valve = SUPERVISORY
TRI - for the following address is located above the door to the TR-30 area (CA B1)
4-027-010 RCA3 B1 MAIN SPRINK VLV . . . .TS . . . . Tamper switch on Main Sprinkler Valve, B1 at doorway to TR30 area
TRI - for the following two addresses is located in the SE corner of the stairwell, 9' above the floor
4-027-011 RCA3 G SPRINKLERS . . . . . . FS . . . . Sprinklers flow switch for Ground floor
4-027-012 RCR3 G SPRINKLER TAMPER . . . TS . . . . Tamper switch on 027-011 valve = SUPERVISORY
TRI - for the following two addresses is located in the SE corner of the stairwell, 9' above the floor
4-027-013 RCA3 L1 SPRINKLERS . . . . . . FS . . . . Sprinklers flow switch for L1 floor
4-027-014 RCA3 L1 SPRINKLER TAMPER . . . TS . . . . Tamper switch on 027-013 valve = SUPERVISORY
TRI - Module for the following two addresses is located in the generator enclosure above the control panel
4-028-001 RCA3 G GENERATOR RUNNING . . . CI . . . . Indicates Generator is running = SUPERVISORY
4-028-002 RCA3 G GENERATOR TROUBLE . . . CI . . . . Generator may not be ready to start = SUPERVISORY
4-028-003 RCA3 G CONTROL RM W EXIT . . . MS . . . . Pull station, at West door, to exterior
4-028-004 RCA3 G PROD SUPPORT EXIT . . . MS . . . . Pull station, at door to exterior
4-028-005 RCA3 G EXIT TO STAIRS . . . . MS . . . . Pull station, at door to stairs
4-028-006 RCA3 L1 EXIT TO CA . . . . . . MS . . . . Pull station, at door to Chemistry Annex
4-028-007 RCA3 L1 OFFICE WEST EXIT . . . MS . . . . Pull station, at West door
4-028-008 RCA3 L1 OFFICE EAST EXIT . . . MS . . . . Pull station, at East door
4-028-009 RCA3 L1 EXIT TO STAIRS . . . . MS . . . . Pull station, at door to stairs
4-028-010 RCA3 L2 TOP OF STAIRS . . . . SMK P  . . Smoke detector on ceiling at top of stairwell
4-028-011 RCA3 L2 AHU#3 DUCT SMOKE . . . SMK D . . Smoke detector in air duct, on South side
4-028-012 RCA3 L2 LOADING BAY EXIT . . . MS . . . . Pull station, at double hoist doors onto roof
4-028-013 RCA3 L2 PENTHOUSE EXIT . . . . MS . . . . Pull station, at door to stairs
TRI - for the following two addresses is located in the L2 Lobby, SE corner, 9' above the floor
4-028-014 RCA3 L2 SPRINKLERS . . . . . . FS . . . . Sprinklers flow switch for L2 floor (Penthouse)
4-028-015 RCA3 L2 SPRINKLER TAMPER . . . TS . . . . Tamper switch on 028-014 valve = SUPERVISORY
1-034-001 ARIEL ALARM TO FIRE DEPT . . . CO . ARIEL ALARM to Transponder, Relay in MOB XLS. ZONE 4
1-034-002 ISAC ALARM TO FIRE DEPT . . . CO . ISAC & ISACII ALARM to Transponder, Relay in MOB XLS. ZONE 3
1-034-003 INSIDE FENCE ALARM . . . . . . CO . . Alarm to Transponder, Relay in MOB XLS. ZONE 2
1-034-004 OUTSIDE FENCE ALARM . . . . . CO . . Alarm to Transponder, Relay in MOB XLS. ZONE 1
1-034-005 MOB 120VAC STROBE LIGHTS . . . V . . Red Strobe Light Outside MOB on North West corner. Relay in MOB XLS
1-034-006 MOB DOOR HOLDERS . . . . . . . CO . . Releases all Fire doors, in MOB. Relay in MOB XLS
Changes are due to 2021/2022 upgrade:
1-035-001 MOB G LOBBY PULL STATION . . . MS . . Pull Station, door 30, Main Lobby West double doors
1-035-002 MOB L1 AHU#6 CONTROL RELAY . . CO . . AHU#6 Fan shutdown
1-035-003 MOB G S. HALL PULL STN East. . MS . . Pull Station, South Hallway, East
1-035-004 MOB G S. HALL PULL STN West. . MS . . Pull Station, South Hallway, West
1-035-005 MOB G E. HALL PULL STN Centre. MS . . Pull Station, East Hall Centre, by door 39
1-035-006 MOB G E. HALL PULL STN Mail. . MS . . Pull Station, East Hall Centre, by Mail Room
1-035-007 MOB G E. HALL PULL STN Purch . MS . . Pull Station, door 33, East, Purchasing Office
1-035-009 MOB L2 N. AHU#1 DUCT . . . . . DS . . MOB North Roof, AHU-1
1-035-010 MOB L1 South Hall Centre . . . SMK . MOB L1, South hall, outside Room 118
1-035-011 MOB L1 S HALL PULL STN West. . MS . . Pull Station, L1 Floor, South Hallway, West
1-035-111 MOB L1 S HALL PULL STN East. . MS . . Pull Station, L1 Floor, South Hallway, East
1-035-012 MOB L1 AUDIT. PULL STN South . MS . . Pull Station, Auditorium Exit door South
1-035-112 MOB L1 AUDIT. PULL STN North . MS . . Pull Station, Auditorium Exit door North
1-035-013 MOB G SW RM 43, JANITOR. . . . HD . . Room 43, Janitor room, South West corner
1-035-014 MOB G W.ELEC SHOP RM39 . . . . HD . . Room 39 is in the North West corner of room 37
1-035-015 MOB G S.W. XFMR RM #38 . . . . HD . . Room 38, South West Transformer room
1-035-016 MOB G S.E. XFMR RM #31 . . . . HD . . Room 31, South East Transformer room
The previous two devices acn be accessed from outside building near South East entrance, door 35
1-035-017 MOB L1 NW RM 81, JANITOR . . . HD  . . L1 Floor, room 81, North West corner, Janitor room
1-035-018 MOB G RM 37, W ELEC SHOP . . . SMK . . Room 37, Ground Floor, South Hall, Electrical Shop
1-035-019 MOB L1 TOP S.W. STAIRS . . . . SMK . . Top of South West stairs
1-035-020 MOB L1 TOP N.W. STAIRS . . . . SMK . . Top of North West stairs
1-035-021 MOB L1 ROOM 97 . . . . . . . . SMK . . Room 97
1-035-022 MOB L1 TOP S.E. STAIRS . . . . SMK . . Top of South East stairs
1-035-023 MOB L2 S. AHU #5 SUP . . . . . DS . . MOB L1 North hall by room 84, AHU-5 Supply Duct (also see 035-030 & 035-031 for fan shutdown)
1-035-024 MOB L1 S. AHU#6 RET DUCT . . . DS . . MOB South Roof AHU-6 duct located L1 South hall, North side, near rooms 124/125,
above ceiling, above cable tray
1-035-025 MOB L2 S. AHU#3 SUP DUCT . . . DS . . MOB East Roof AHU-3 Supply duct, on North side
1-035-026 MOB L2 S. AHU#3 RET DUCT . . . DS . . MOB East Roof AHU-3 Return duct, on North side
1-035-027 MOB L1 N. HALL PULL STN. . . . MS . . .Pull Station, L1 Floor, North Hallway, Centre
1-035-127 MOB L1 N. HALL PULL STN. . . . MS . . .Pull Station, L1 Floor, North West stairs
In the ceiling above the Auditorium North stairs, on the South wall
1-035-028 MOB L1 BOARD RM AHU #2 . . . . DS . . MOB Board Room AHU-2
above the ceiling in the hallway above the Board room South door (above the electrical box covers)
1-035-029 MOB L1 BOARD RM AHU 2+3 . . . CO . . AHU 2 + 3 SHUTDOWN
1-035-030 MOB L2 S AHU #5 B . . . . . . CO . . AHU-5 SHUTDOWN
1-035-031 MOB L2 S AHU #5 C . . . . . . CO . . AHU-5 SHUTDOWN
1-035-032 MOB L1 AHU#7 DS#1 . . . . . . DS . . AHU#7 Fan Shutdown
1-035-033 MOB L1 AHU#7 DS#2 . . . . . . DS . . AHU#7 Fan Shutdown
1-035-034 MOB L2 AHU #8 DS . . . . . . . CO . . AHU#8 Fan Shutdown
1-035-035 MOB L2 AHU #9 DS . . . . . . . CO . . AHU#9 Fan Shutdown
1-035-036 MOB L2 AHU#10 DS . . . . . . . CO . . AHU#10 Fan Shutdown
1-035-037 MOB G N. HALL PULL STN NW . . MS . . Pull Station, door 32, Ground Floor North West
1-035-137 MOB G N. HALL PULL STN Centre. MS . . Pull Station, Ground Floor, North Hallway, Centre
1-035-038 MOB G CAFE. EXTINGUISHER . . . CI . . Cafeteria Grill Extinguishing System
in MOB room 38, North wall
1-035-039 MOB DR#39 LOCK RELEASE . . . . CO . . MOB Alarm input to Card Access system. Unlocks door #39
1-035-040 MOB G ELEVATOR LOBBY . . . . . SMK . . Ground Floor, Elevator Lobby ceiling
Ground floor Lobby. in ceiling at east end
1-035-041 MOB G NW DOOR RELEASE . . . . CO . . Module to release (depower) the fire door holder
1-035-042 MOB G ELEVATOR LOBBY . . . . . MS . . Pull Station Ground floor in MOB Elevator Lobby
1-035-043 MOB L1 ELEVATOR LOBBY. . . . . SMK . L1 floor, Elevator Lobby ceiling
1-035-044 MOB L1 ELEV TOP OF SHAFT . . . SMK . Top of elevator shaft
1-035-045 MOB L1 ELEV MACHINE RM . . . . SMK . .L1 floor, Elevator Lobby, inside door of Elevator machine control room
1-035-046 MOB G SE STAIRS P.S. . . . . . MS . . Pull Station, Ground floor, South East stairwell door
1-035-047 Badge Room Smoke . . . . . . . SMK . Smoke Deteector on Badge Room ceiling
1-035-048^1 MOB G UNDER AUDITORIUM TS . . . . TS . Main valve, Glycol sprinklers under Auditorium - Supervisory
1-035-048^2 MOB G UNDER AUDITORIUM BACKFLOW . TS . Two of: Backflow preventer service valve for the above - Supervisory
1-035-049^1 MOB G Sprinkler Backflow Inlet. . TS . Backflow preventer inlet valve - Supervisory
1-035-049^2 MOB G Sprinkler Backflow Outlet . TS . Backflow preventer outlet valve - Supervisory
1-035-050^1 MOB G SPRINKLER FLOW. . . . . . . FS . Ground floor Sprinklers
1-035-050^2 MOB G MAIN SPRINKLER TAMPER . . . TS . Main Sprinkler Valve tamper switch - Supervisory
1-035-051^1 MOB L1 SPRINKLER FLOW . . . . . . FS . L1 Floor Sprinklers
1-035-051^2 MOB FIRE HOSE CAB. TAMPER . . . . TS . Fire Hose Cabinets Main Valve for 1-035-059 - Supervisory
1-035-052^1 MOB G Sprinkler Tamper. . . . . . TS . Main Sprinkler Valve for 1-035-053 - Supervisory
1-035-052^2 MOB L1 Sprinkler Tamper . . . . . TS . Valve for 1-035-055 - Supervisory
1-035-053 MOB G FIRE HOSE STANDPIPE FLOW. . . FS . Water flow from any of the 7 hose cabinets - Supervisory
1-035-055 TRAILER Hh Pull Station Door Hh2 . . MS. . Pull Station, Door Hh2, East
1-035-056 TRAILER Hh West open office area . . SMK . in the West open office area
1-035-057 TRAILER Hh Mens Washroom . . . . . . HD . . Mens Washroom, note: Hot water tank in wall near door
1-035-058 TRAILER Hh Ladies Washroom . . . . . HD. . Ladies Washroom
1-035-059 TRAILER Hh East open office area . . SMK . East open office area, North West, in skylight well
1-035-060 TRAILER Hh East open office area . . SMK . East open office area, North East, in skylight well
1-035-061 TRAILER Hh East open office area . . SMK . East open office area, South West
1-035-062 TRAILER Hh East open office area . . SMK . East open office area, South East
1-035-063 TRAILER Hh Kitchen area. . . . . . . HD. . Kitchen, area near room 11
1-035-064 TRAILER Hh Room 11 Janitor . . . . . HD. . Room 11, Janitor
1-035-065 TRAILER Hh Pull Station Door Hh1 . . MS. . Pull Station, Door Hh1, West
1-035-066 TRAILER Hh near West doors . . . . . SMK . near West doors, by room 1
TRI - In Trailer Hh, South East corner
1-035-067 TRAILER Hh ELR . . . . . . . . . . . CO . . Shuts down Trailer Hh HVAC
TRI - at door Hh1, North West corner
1-035-068 TRAILER Hh POWER SUPPLY. . . . . . . CI . . Monitors P.S. for bell circuit , TROUBLE
MAIN OFFICE BUILDING - continued
Ground Floor :
L1 Floor :
1-037-002 MOB BELL CCT. NORTH WING
Ground Floor :
L1 Floor :
E-Linac COMPRESSOR BUILDING , XLS - 8
8-041-001 ECOMP G WATER SUP RM PS . . . MS . . Pull Station West side, North end, Water Supply Room
8-041-002 ECOMP G COMPRESSOR RM PS . . . MS . . Pull Station East side at personnel entrance door to Compressor Room
8-041-003 ECOMP G STAIRS TO L1 PS . . . MS . . Pull Station East side at foot of stairs to level L1
8-041-004 ECOMP G MAINT RM PS . . . . . MS . . Pull Station East side, North, at personnel entrance door to Maintenance Room
8-041-005 ECOMP G WOMENS WC PS . . . . . MS . . Pull Station North side, West, Womens washroom and shower facility
8-041-006 ECOMP G MENS WC PS . . . . . . MS . . Pull Station North side, Centre, Mens washroom and shower facility
8-041-010 ECOMP G WOMENS WC HEAT . . . . HD . . North side, West, womens washroom and shower facility
8-041-011 ECOMP G MENS WC HEAT . . . . . HD . . North side, Centre, Mens washroom and shower facility
All Valves and Flow Switches are located in the Water Supply Room (west side, north end)
8-041-016 ECOMP L1 SPRINKLER VALVE . . . . . . TS . . Tamper switch on valve for 8-041-015 = SUPERVISORY
8-041-018 ECOMP COMP RM SPRINK VALVE . . . . . TS . . Tamper switch on valve for 8-041-017 = SUPERVISORY
8-041-020 ECOMP G SPRINKLER VALVE . . . . . . TS . . Tamper switch on valve for 8-041-019 = SUPERVISORY
8-041-022 ECOMP CANOPY SPRINKLER VALVE . . . . TS . . Tamper switch on valve for 8-041-021 = SUPERVISORY
8-041-023 ECOMP CANOPY SPRINKLER LOW AIR . . . CI . . Canopy sprinklers, Dry system, Low Air Pressure = TROUBLE
IMPORTANT INSTRUCTION: IF THIS SYSTEM IS ACTIVATED, IT MUST BE DRAINED AND RESET BY THE SPRINKLER SERVICE COMPANY.
See "Service Providers"
8-041-024 ECOMP SPRK BCKFLOW VALVE1&2 . . . . TS . . Tamper switches on both valves = SUPERVISORY
8-041-025 ECOMP SPRINKLER MAIN VALVE . . . . . TS . . Tamper switch on MAIN WATER SUPPLY valve = SUPERVISORY
8-042-001 ECOMP L1 TOP OF STAIR PS . . . . . . MS . . Pull Station at top of stairs to Storage level L1
8-042-002 ECOMP L1 STORAGE SMOKE . . . . . . SMK . . on ceiling of L1 Storage Area, West side
8-042-003 ECOMP L1 TOP OF MAINT . . . . . . . SMK . . on ceiling high above Maintenance Workshop (barely visible above duct)
8-042-004 ECOMP L1 COMP RM EAST SMK . . . . . SMK . . Compressor room, ceiling, East side
8-042-005 ECOMP L1 COMP RM WEST SMK . . . . . SMK . . Compressor room, ceiling, West side
8-042-006 ECOMP L1 HVAC DUCT SMK . . . . . . SMK . . in HVAC duct (actual location unknown)
8-042-007 ECOMP L1 TOP OF STAIR SMK . . . . . SMK . . at top of stairs to Storage level L1
8-042-010 ECOMP L1 HVAC CONTROL AHU/R03 . . . CO . . HVAC Fan Shutdown (controlled from 8-042-006)
8-043-001 2nd Fl Storage/Maint. Bell cct. B1 . CO . ECOMP L1 Bells
8-043-002 Grnd Floor Bell cct B2 . . . . . . . CO . ECOMP Ground Floor Bells
8-043-003 Grnd Floor Strobe cct S1 . . . . . . CO . Includes washrooms
8-043-004 Strobe cct S2 Outside North S2 . . . CO . on building north wall, NE corner
8-043-005 Strobe cct S3 Water Heater rm S3 . . CO . in L1 water heater room
ISAC 1 BUILDINGS , XLS - 5
5-051-001 ISAC TMB B2 S HOTCELLS W . . SMK I . . South Hotcells service area, West side
5-051-002 ISAC TMB B2 S HOTCELLS E . . SMK I . . South Hotcells service area, East side
5-051-003 ISAC TMB B2 N HOTCELLS E . . SMK I . . North Hotcells service area, East side
5-051-004 ISAC TMB B2 N HOTCELLS W . . SMK I . . North Hotcells service area, West side
5-051-005 ISAC TMB B1 TGT HALL ENT . . SMK I . . Entrance corridor into Target Hall
5-051-006 ISAC TMB B1 CNTL ZONE E . . SMK I . . Target Hall entrance service area, East
5-051-007 ISAC TMB B1 CNTL ZONE W . . SMK I . . Target Hall entrance service area, West
5-051-008 ISAC TMB B1 T.H. LAUNDRY . . SMK I . . Target Hall entrance service area, Laundry room
5-051-009 ISAC TMB B1 EXIT NE STAIR . MS . . . .Pull Station, at Emergency Exit stairs from Target Hall service area
5-051-010 ISAC EXP.HALL ACCEL C.R. . . SMK I . . Experimental Hall, ground floor, East side of centre block
VESDA Fault or VESDA power supply Fault or VESDA Alert Level - TROUBLE
5-051-012 ISAC EXPHAL G TRILIS ACTION. SMK . . . TRILIS VESDA at low (pre-Alarm) status = SUPERVISORY
- - - Note : See 5-051 -059 and -060 for TRILIS VESDA Alarm and Suppression system activation - - -
5-051-014 ISAC EXPHAL G ROOM 116 . . . SMK I . . Experimental Hall, ground floor, centre block, Room 116
5-051-015 ISAC EXPHAL G COMM RM 115 . SMK I . . Experimental Hall, ground floor, centre block, Room 115
TRI - Experimental Hall, ground level South, room 116
5-051-016 ISAC EXPHAL G RCKRM L1 TS . . TS . . . Tamper Switch on sprinkler valve in room 116, Exp. Hall G South, which supplies L1
(Low and High energy Counting rooms) = SUPERVISORY
TRI - for the following two addresses, Room 113, Janitor
5-051-017 ISAC EXPHAL S SPRINK FS . . . FS . . . FS on sprinkler system which feeds the heads for the entire G and L1 centre block of rooms.
5-051-018 ISAC EXPHAL JAN SPRNK TS. . . TS . . . .Tamper switch for 051-017 = SUPERVISORY
5-051-019 ISAC EXPHAL G,E DOOR P.S. . . MS . . . Pull Station, door 97, East
5-051-020 ISAC EXPHAL G,N DOOR P.S. . . MS . . . Pull Station, door 98, North
TRI - for the following two addresses, Experimental Hall, North East Corner
5-051-021 ISAC EXPHAL G,NE SPRNK FS . . FS . . . ISAC Exp. Hall North East corner.
5-051-022 ISAC EXPHAL G,NE SPRNK TS . . TS . . . Tamper switch for 051-021 = SUPERVISORY
For sprinkler heads above the main sprinkler valves. Switch cover off = TROUBLE
TRI - Experimental Hall North East Corner
5-051-023 ISAC EXPHAL MAIN SPRNK FS . . FS . . . ISAC Exp. Hall North East Corner.
Alarms if any sprinkler water flows for more than 45 seconds. Switch cover off = TROUBLE
TRI - Experimental Hall North East Corner
5-051-024 ISAC EXPHAL MAIN SPRNK TS . . TS . . . ISAC Exp. Hall North East Corner.
TWO valves in series with the Main supply line, either side of the backflow preventer.
Either Tamper switch operated = SUPERVISORY
Either Tamper switch cover off = TROUBLE
TRI - Experimental Hall North East Corner
5-051-025 ISAC EXPHAL MAIN SPRNK TS . . TS . . . ISAC Exp. Hall North East Corner.
Main water supply valve for the ISAC buildings.
Tamper switch operated = SUPERVISORY
Tamper switch cover off = TROUBLE
TRI - ISAC Exp. Hall North East corner, Mezzanine level, North wall, near top of stairs.
5-051-026 ISAC EXPHAL RTU-1 SHUTDWN . . CO . . . Roof Top Air Handling Unit 1, Shutdown.
5-051-027 ISAC EXPHAL L1 HI-EN CR . . . SMK I . . Experimental Hall, L1 floor, East side, High energy control room.
5-051-028 ISAC EXPHAL L1 LOW-EN CR . . SMK I . . Experimental Hall, L1 floor, West side, Low energy control room.
TRI - for the following two addresses, In cabinet in B2 Lobby -
5-051-029 ISAC TMB B2 LOBBY SPNK FS . . FS . . . In the cabinet in the B2 Lobby area.
Flow Switch, Main sprinkler supply for TMB B2 floor areas:
5-051-030 ISAC TMB B2 LOBBY SPNK TS . . TS . . . Tamper Switch for 051-029 = SUPERVISORY
5-051-031 ISAC TMB B2 LOBBY DOOR PS . . MS . . . Pull Station, in B2 Lobby Area near elevator
5-051-032 ISAC TMB B2 TUNNL MAZE PS . . MS . . . Pull Station, inside Tunnel Maze at Emergency Exit door
5-051-033 ISAC TMB B2 LOBBY SMOKE . . . SMK I . . B2 floor lobby, area around Elevator
5-051-034 ISAC TMB B2 SAFETY OFFICE . . SMK I . . B2 floor, to East of lobby
TRI - Active Service Room, TMB B2, near door 002, on ceiling -
5-051-035 ISAC TMB B2 TRINAT SPK TS . . TS . . . In Active Service room, TMB B2, near door 002.
Tamper switch for sprinklers in room 012, TRINAT, Exp. Hall B1 = SUPERVISORY
TRI - Active Service Room, TMB B2, near door 002, on ceiling.
5-051-036 ISAC TMB B2 CNTL ZN SP TS . . TS . . . In Active Service room, TMB B2, near door 002.
Tamper switch for room 08 & 09, Target Hall Entrance area, room 13 Shower & room 14 Laundry = SUPERVISORY
5-051-037 ISAC ALM TO DDC/INTERFACE . . RLY . . . TROUBLE ONLY . . TRI - In XLS panel TMB B1, room 02
TRI - TMB B1 Lobby, above door 03
5-051-038 ISAC TMB B1 LOBBY SPNK TS . . TS . . . For room 03, TMB B1, Ion Source Control room, outside room 03 = SUPERVISORY
TRI - TMB B1 Lobby, above door 04
5-051-039 ISAC TMB B1 LOBBY SPNK TS . . TS . . . For room 05, TMB B1, Remote Handling Control room, outside room 04 = SUPERVISORY
TRI - for the following two addresses, In cabinet in TMB B1 Lobby
5-051-040 ISAC TMB B1 LOBBY SPNK FS . . FS . . . In cabinet in TMB B1 Lobby, room 01
5-051-041 ISAC TMB B1 LOBBY SPNK TS . . TS . . . Tamper Switch for 051-040 = SUPERVISORY
Sprinkler system supplying the Hallway, room 6 & room 7.
5-051-042 ISAC TMB B1 CR RM . . . . . . SMK I . . room 003, Target and Ion Source Control room
5-051-043 ISAC TMB B1 FIRST-AID RM . . SMK I . . room 004, First-Aid
5-051-044 ISAC TMB B1 R.H. C.R. . . . . SMK I . . room 005, R.H. Control room, Target Hall Crane controls on West Wall
5-051-045 ISAC TMB B1 ASSMBLY RM . . . SMK I . . room 006, component assembly
5-051-046 ISAC TMB B1 COLD LAB . . . . SMK I . . room 007, Cold Lab, at end of Hall
5-051-047 ISAC TMB B1 LOBBY SMOKE . . . SMK I . . Area near Elevator
5-051-048 ISAC TMB B1 LOBBY DOOR PS . . MS . . . Pull Station, South building B1, stairwell
5-051-049 ISAC TMB G SOUTH STAIR PS . . MS . . . Pull Station, door 94, South Bldg Main door
5-051-050 ISAC TMB L1 S. STAIR PS . . . MS . . . Pull Station, South building, Floor L1, stairwell
5-051-051 ISAC TMB L1 TOP S. STAIR . . SMK I . . South Building Floor L1, Ceiling of stairwell
5-051-052 ISAC TMB L1 TOP ELEV SHFT . . SMK I . . Top of Elevator Shaft
TRI - In ISAC Exp. Hall North East Corner -
5-051-053 ISAC EXPHALL G N/E SPRNK . . CI . Low Water Pressure switch on the Main Supply Line. Building water pressure low
Low Pressure = SUPERVISORY
Switch cover off = TROUBLE
5-051-054 ISAC EXPHAL SERV SHFT TOP . . SMK I . . detector at top of communications, cabling and services shaft. Access via double doors in South
wall on level L1.
5-051-055 ISAC TUDA ROOM DUCT . . . . . SMK I . . ISAC Experimental Hall, TUDA Room, HVAC return duct
TRI - for the following two addresses, ISAC Experimental Hall, North East Corner
5-051-056 ISAC GAS SHACK . . CI . . .
- module monitoring the following two devices -
5-051-057 SPARE ZONE . . . . . not in use
5-051-058 ISAC EXPHALL N BEAM LINK . . SMK . . . Smoke detector, in ISAC 1 above Beam Link, on underside of mezzanine support beam.
NOTE : ALARMS both Node 5 (ISAC) and Node 6 (ISAC II) and activates ISACII Ground Floor pre-action sprinkler system.
5-051-059 ISAC EXPHALL TRILIS RM FIRE1. SMK . . . VESDA system, ISAC Experimental Hall Room 116. Monitoring room 112, TRILIS. ALARM due to smoke detected.
Bells ring at this level.
5-051-060 ISAC EXPHALL TRILIS RM FIRE2. SMK . . . VESDA system operates a solenoid to charge the sprinkler lines. This FIRE2 level is a higher Alarm level
than previous, thus requiring suppression system to be activated.
- Note: Water will not flow until a sprinkler head is activated
5-052-001 ISAC TMB B2 MSPIT W DOOR . . MS . . . Pull Station, at foot of emergency escape ladder
5-052-002 ISAC EXPHAL B1 TRINAT PS . . MS . . . Pull Station, at exit door in TRINAT room
TRI - for the following two addresses, ISAC Experimental Hall, South West corner
5-052-003 ISAC GENERATOR RUNNING . . . CI . . . Indicates generator is running = SUPERVISORY
5-052-004 ISAC GENERATOR TROUBLE . . . CI . . . Generator may not be ready to start = SUPERVISORY
5-052-005 ISAC TMB G RM 92 RH SHOP . . HD . . . Ground floor, Remote Handling Shop
5-052-006 ISAC TMB G RM 92 RH SHOP . . MS . . . Pull Station Ground floor, door 92, Remote Handling Shop
5-052-007 ISAC EXPHAL G SW STAIR PS . . MS . . . Pull Station, door 91, stairwell ground level Exit
TRI - for the following two addresses, ISAC Experimental Hall, South West corner, Mezzanine level, on the South wall, just East of the transformers
5-052-008 ISAC EXPHAL RTU-2 STOPRLY . . CO . . . Roof Top Air Handling Unit 2, shuts unit down.
5-052-009 ISAC EXPHAL AHU-2 STOPRLY . . CO . . . Air Handling Unit 2, shuts unit down
5-052-010 ISAC TMB B1 EL.SERV RM HD . . HD . . . Electrical Services room, above UPS
5-052-011 ISAC TMB B1 EL.SERV RM . . . SMK I . . Electrical Services room, above rack 3A
TRI - TMB L2, Penthouse, on South side of filter room across from pump P-4.
5-052-012 ISAC SF-1 START RELAY . . . . CO . . . SUPPLY FAN 1
In the event of Alarm, STARTS Pressurization Fan 1 for TMB building South stairwell.
5-052-013 ISAC TMB G COMM ROOM 104A . . HD . . . Communications wiring room, enter through room 104
5-052-014 ISAC TMB G COMM ROOM 104A . . SMK I . . Communications wiring room, enter through room 104
5-052-015 ISAC TMB G STORAGE RM 104 . . SMK I . . Storage room across from South double doors
5-052-016 ISAC TMB G ION SRC RM N . . . SMK I . . Stable Ion Source room, 103, to West of double doors
5-052-017 ISAC TMB G ION SRC RM S . . . SMK I . . Stable Ion Source room, 103, to West of double doors
TRI - room 102, TMB ground (West of elevator) -
5-052-018 ISAC TMB G MAT.BAY SPK TS . . TS . . . For room 103, TMB G, Stable Ion Source room = SUPERVISORY
5-052-019 ISAC TMB G MAT. BAY . . . . . SMK I . . Area to the West of the Ground level Lobby
5-052-020 ISAC TMB G JANITOR RM . . . . SMK I . . Ground floor, room 105, Janitors room
5-052-021 ISAC TMB G MENS W.C. . . . .SMK I . . Ground floor, room 106, Mens washroom
5-052-022 ISAC TMB G LADIES W.C. . . .SMK I . . Ground floor, room 107, Ladies washroom
5-052-023 ISAC TMB G MEETING RM . . . . SMK I . . Ground floor, room 108, East of Lobby
5-052-024 ISAC TMB G OFFICE WEST . . . .SMK I . . Ground floor, room 109, West section of office area
5-052-025 ISAC TMB G OFFICE EAST . . . .SMK I . . Ground floor, room 109, East section of office area
5-052-026 ISAC TMB G LOBBY SMOKE . . . .SMK I . . Ground floor lobby, area near Elevator
TRI - for the following two addresses, In cabinet in TMB G Lobby -
5-052-027 ISAC TMB G MATBAY SPK FS . . .FS . . . In cabinet in room 102 (area West of lobby)
5-052-028 ISAC TMB G MATBAY SPK TS . . .TS . . . Tamper Switch for 052-027 = SUPERVISORY
Supplies TMB Ground level, except for room 103, Stable Ion Source room.
5-052-029 ISAC TMB L2 HEPA RM 203 . . . SMK I . . HEPA Filter room, Penthouse Centre, East of door
5-052-030 ISAC TMB L2 BOILER RM 204 . . SMK I . . Boiler room, Penthouse East End
5-052-031 ISAC TMB PENTHOUSE EAST . . . SMK I . . Penthouse, East end, above AC compressor coil access door
5-052-032 ISAC TMB PENTHOUSE CENTRE . . SMK I . . Penthouse, Centre section, by HEPA room 203
5-052-033 ISAC TMB PENTHOUSE WEST . . . SMK I . . Penthouse, West end, South of pump P-1
5-052-034 ISAC TMB PENTHOUSE W HD . . . HD . . . Penthouse, West end, South of pump P-1
5-052-035 ISAC TMB PENTHOUSE DOOR . . . MS . . . Pull Station, door 100, TMB L2, Penthouse
TRI - TMB L2, Penthouse, centered on AHU-1 -
5-052-036 ISAC TMB AHU-1 STOP RELAY . . CO . . . Shuts down Air Handling Unit 1
TRI - for the following two addresses, In cabinet in TMB L2, Penthouse. South of P3
5-052-037 ISAC TMB PENTHOUSE SPK FS . . FS . . . Penthouse, TMB L2, in P.H. South of P3
5-052-038 ISAC TMB PENTHOUSE SPK TS . . TS . . . Tamper Switch for 052-037 = SUPERVISORY
5-052-039 ISAC TMB L1 MENS W.C. . . . SMK I . . Floor L1, room 210, Mens washroom
5-052-040 ISAC TMB L1 WOMENS W.C. . . SMK I . . Floor L1, room 208, Womens washroom
5-052-041 ISAC TMB L1 E. DES.OFF W . . SMK I . . East Design Office, West area
5-052-042 ISAC TMB L1 E. DES.OFF E . . SMK I . . East Design Office, East area
5-052-043 ISAC TMB L1 E. EMRG DOOR . . MS . . . Pull Station, door 99, East Design Office, door to East Emergency Exit stairs
5-052-044 ISAC TMB L1 DES.OFF. LBBY . . SMK I . . L1 floor lobby, area near Elevator
5-052-045 ISAC TMB L1 W. DES.OFF . . . SMK I . . West Design Office
5-052-046 ISAC TMB L1 LUNCH ROOM . . . SMK I . . Design Office Lunch room, to East of elevator
5-052-047 ISAC TMB L1 ELV.MACH.RM . . . SMK I . . Elevator Machine room, next to elevator shaft
TRI - for the following two addresses, In cabinet in TMB L1 Lobby
5-052-048 ISAC TMB L1 DESOFF SPK FS . . FS . . . Design Office, in TMB L1 Lobby cabinet
5-052-049 ISAC TMB L1 DESOFF SPK TS . . TS . . . Tamper Switch for 052-048 = SUPERVISORY
5-052-050 ISAC EXPHAL B1 TRINAT S/W . . HD . . . Detector in South West area of TRINAT room
5-052-051 ISAC EXPHAL B1 TRINAT S/C . . HD . . . Detector in South Centre area of TRINAT room
5-052-052 ISAC EXPHAL B1 TRINAT S/E . . HD . . . Detector in East area of TRINAT room
5-052-053 ISAC TMB G OFFICE E DOOR . . .MS . . . Pull Station, door 95, East Exit
5-052-054 ISAC TMB G SERV SHAFT TOP . . SMK I . . Detector at top of comm., cabling and services shaft. Access via double doors in room 104A.
5-052-055 ISAC TMB G MAT BAY DOOR . . . MS . . . Pull Station, door 93, South double doors
5-052-056 ISAC EXP HALL SW STAIRS . . . SMK . . . Detector on ceiling of stairwell. Egress route from TRINAT and Experimental Hall.
5-052-057 ISAC EXPHALL B1 TRINAT RM FAULT . . . . TRINAT VESDA system, ISAC Experimental Hall B1 Room 012, monitoring TRINAT room.
VESDA Fault or VESDA Power Supply Fault or VESDA Alert Level = TROUBLE
5-052-058 ISAC EXPHALL B1 TRINAT RM ACTION. . . . TRINAT VESDA system detects smoke at low (pre-Alarm) status = SUPERVISORY
5-052-059 ISAC EXPHALL B1 TRINAT RM FIRE1 SMK . . TRINAT VESDA system detects smoke at higher level = ALARM
CZM - inside XLS, ISAC B1, room 02, Electrical room
5-053-001 ISAC TMB B2 2A TUNNEL
- module monitoring the following 3 devices -
CZM - inside XLS, ISAC B1, room 02, Electrical room
5-053-002 ISAC TMB B2 SEPARATOR PIT
- module monitoring the following 4 devices -
CZM - inside XLS, ISAC B1, room 02, Electrical room
5-053-003 ISAC TMB B2 MECH. RM HD
- module monitoring the following 2 devices -
CZM - inside XLs, ISAC B1, room 02, Electrical room
5-053-004 ISAC EXPHAL B1 TRINAT N
- module monitoring the following 3 devices -
Three Explosion Proof Heat Detectors on the North side of the TRINAT room (ISAC B1).
SEE ALSO: 052-050, 052-051, 052-052
CZM - location unknown
5-054-001 ISAC TGT HALL BEAM DET. . . . SMKB . . Transmitter and Receiver mounted at East and West
ends of TARGET HALL, four feet below roof, above
South crane track.
Note: may be set off by workers on top of crane.
CZM - location unknown
5-054-002 ISAC EXPHAL S BEAM DET . . . SMKB . . Transmitter and Receiver mounted at East and West
ends of EXPERIMENTAL HALL on top of SOUTH
vertical column.
Note: may be set off by workers on top of crane.
CZM - location unknown
5-054-003 ISAC EXPHAL CNTR BEAM DET . . SMKB . . Transmitter and Receiver mounted at East and West
ends of EXPERIMENTAL HALL on top of CENTRE vertical column.
Note: may be set off by workers on top of crane.
CZM - location unknown
5-054-004 ISAC EXPHAL N BEAM DET . . . SMKB . . Transmitter and Receiver mounted at East and West
ends of EXPERIMENTAL HALL on top of NORTH vertical column.
Note: may be set off by workers on top of crane.
For Exp Hall level L1, Low and High Energy counting rooms.
For room 103, TMB G, Stable Ion Source room.
For room 03, TMB B1, Ion Source Control room,
For room 05, TMB B1, Remote Handling Control room
5-056-001 ISAC SPRNK SOL #5 TMB . . . . SOL . . . TMB B2 Lobby. Large solenoid valve at ceiling
Main sprinkler supply for TMB B2 floor areas: Stairwell, Lobby, rm 004 Safety Office, rm 006
Hot cells South, 010 Hot cells North.
5-056-002 ISAC SPRNKSOL #6 THCNTLZN . . SOL . . . TMB B2, Active Service room, near door 002
For rooms 08 & 09, Target Hall Entrance area; room 13 Shower & room 14 Laundry.
5-056-003 ISAC SPRNK SOL #7 TRINAT. . . SOL . . . TMB B2, Active Service room, near door 002
For room 012, TRINAT Exp. Hall B1,
5-057-001 ISAC BELL CIRCUIT #1
5-057-002 ISAC BELL CIRCUIT #2
5-057-003 ISAC BELL CIRCUIT #3
6-061-002 ISAC2 G ELECTRICAL RM E . . SMK . . East side of Electrical room, #165
6-061-003 ISAC2 G ELECTRICAL RM W . . SMK . . West side of Electrical room, #165
6-061-004 ISAC2 G ELEC RM S EXIT . . . MS . . Pull Station, Electrical room, #165 South Exit
6-061-005 ISAC2 G CRYO RM S EXIT . . . MS . . Pull Station, Cryogenics room, #164 South Exit
6-061-006 ISAC2 G CRYOGENICS RM . . . SMK . . centre of ceiling, room #164
6-061-007 ISAC2 G RF ROOM SE EXIT . . MS . . Pull Station, South wall, at West wall of Beam Link
6-061-008 ISAC2 G BEAM LINK RM . . . . SMK . . centre of ceiling of Beam Link, room #163
6-061-009 ISAC2 G RF ROOM EAST . . . . SMK . . East side of R.F. room #163
6-061-010 ISAC2 G RF ROOM WEST . . . . SMK . . West side of R.F. room #163
6-061-011 ISAC2 G RF ROOM SW EXIT . . MS . . Pull Station, West wall next to Exit door
6-061-012 ISAC2 G VAULT EXIT TO RF . . MS . . Pull Station, Vault West end, South side of Exit doorway to R.F. room
6-061-013 ISAC2 G VAULT NW EXIT . . . MS . . Pull Station, Vault North West corner, next to Exit door to Lobby
6-061-014 ISAC2 G LOBBY SOUTH EXIT . . MS . . Pull Station, at Lobby Entrance on South wall across from Graphics Panel
6-061-015 ISAC2 G OPEN OFFICE AREA . . SMK . . centre of ceiling, room #130
6-061-016 ISAC2 G WEST HALL EXIT . . . MS . . Pull Station, at Stair #1 next to door
6-061-017 ISAC2 G SCRF PREP EXIT . . . MS . . Pull Station, in West corridor next to door
6-061-018 ISAC2 G SCRF T/R/S AREA . . SMK . . centre of ceiling, room #152
6-061-019 ISAC2 G HALLWAY N EXIT . . . MS . . Pull Station, at Stair #2, next to door
6-061-020 ISAC2 G E CORRIDOR N END . . MS . . Pull Station, in East corridor, next to door
6-061-021 ISAC2 G COM/TEL RM 148 . . . SMK . . centre of ceiling, room #148
6-061-022 ISAC2 G TGT PREP. RM 154 . . SMK . . centre of ceiling, room #154
6-061-023 ISAC2 G GEN. SETUP RM 155. . SMK . . centre of ceiling, room #155
6-061-024 ISAC2 G DETECTOR LAB 156 . . SMK . . centre of ceiling, room #156
6-061-025 ISAC2 G RF CONTROL RM 157 . SMK . . centre of ceiling, room #157
6-061-026 ISAC2 G RM TEMP. TEST 158 . SMK . . centre of ceiling, room #158
6-061-027 ISAC2 G VAULT EAST EXIT. . . MS . . Pull Station, Vault North East corner, on North wall at sliding door
6-061-028 ISAC2 G EXP.HALL NW EXIT . . MS . . Pull Station, Experimental Hall North West corner, at Exit to North corridor
TRI - for the following two addresses is located in XLS-6 (Electrical Room, room 165)
6-061-059 ISAC2 G S STAIR PRES.FAN . . CO . . Stairwell #3 (South) pressurization fan. Starts during an alarm condition.
Located beneath the lowest flight of stairs at ground level.
6-061-060 ISAC2 G AUX P.S. AC LOSS . . CI . . Pre-action Solenoid power supply. Reports loss of AC power to system. SUPERVISORY ONLY
6-062-001 ISAC2 HELIUM BLDG EXIT . . . MS . . Pull Station, West of door
6-062-002 ISAC2 G EXP. HALL S EXIT . . MS . . Pull Station, Experimental Hall South East corner, next to Exit door
6-062-003 ISAC2 G TECH SHOP EXIT . . . MS . . Pull Station, Experimental Hall East side, room #172, on South wall near double door
6-062-004 ISAC2 G TECH SHOP . . . . . SMK . . centre of ceiling, room #172, Experimental Hall East side
TRI - for the following two addresses is located in the Exp. Hall, North East corner, East wall
6-062-005 ISAC2 G RF/CRYO/EL SPRNK . . FS . . Pre-Action Dry sprinkler system for R.F., Cryogenics and Electrical rooms
(Ground floor : room #'s 163, 164, 165), FS located in Experimental Hall North East corner
6-062-006 ISAC2 G RF/CRYO/EL TAMPR . . TS . . Tamper Switch on 062-005 valve = SUPERVISORY
- NOTE : also reference 6-062-007, Low Air Pressure signal for 062-005 pre-action system = SUPERVISORY
IMPORTANT INSTRUCTION: IF THIS SYSTEM IS ACTIVATED, IT MUST BE DRAINED AND RESET BY THE SPRINKLER SERVICE COMPANY.
See "Service Providers"
TRI - for the following two addresses is located in the Exp. Hall, North East corner, East wall
6-062-007 ISAC2 G RF/CRYO/EL L.AIR . . CI . . Low Air Pressure signal for 062-005 pre-action system = SUPERVISORY
6-062-008 ISAC2 L1 PS/COMP LOW AIR . . CI . . Low Air Pressure signal for 062-009 pre-action system = SUPERVISORY
TRI - for the following two addresses is located in the Exp. Hall, North East corner, East wall
6-062-009 ISAC2 L1 PS/COMP SPRINK . . FS . . Pre-Action sprinkler system for Power Supply and Network Computer rooms
(L1 : room #'s 260 & 242) FS located in Experimental Hall North East corner
6-062-010 ISAC2 L1 PS/COMP TAMPER . . TS . . Tamper Switch on 062-009 valve = SUPERVISORY
- NOTE : also reference 6-062-008, Low Air Pressure signal for 062-009 pre-action system = SUPERVISORY
IMPORTANT INSTRUCTION: IF THIS SYSTEM IS ACTIVATED, IT MUST BE DRAINED AND RESET BY THE SPRINKLER SERVICE COMPANY.
See "Service Providers"
TRI - for the following two addresses is located in the Exp. Hall, North West corner, North wall, 14' above floor
6-062-011 ISAC2 G VLT/LABS SPRINK . . FS . . Sprinkler system for Ground floor Vault and Labs, Exp. Hall NW corner, 15' above floor (top piping)
6-062-012 ISAC2 G VLT/LABS TAMPER . . TS . . Tamper Switch on 062-011 valve = SUPERVISORY
TRI - for the following two addresses is located in the Exp. Hall, North East corner, East wall, above door #171
6-062-014 ISAC2 G EXP HALL SPRINK . . FS . . Sprinkler system for Exp. Hall, Exp. Hall NE corner, 13' above floor.
6-062-015 ISAC2 G EXP HALL TAMPER . . TS . . Tamper Switch on 062-014 valve = SUPERVISORY
TRI - for the following two addresses is located in the Exp. Hall, North East corner, East wall
6-062-016 ISAC2 G BKFLOW PREV TS1 . . TS . . Tamper Switch on Backflow Preventer Valve #1, Exp. Hall NE = SUPERVISORY
6-062-017 ISAC2 G BLFLOW PREV TS2 . . TS . . Tamper Switch on Backflow Preventer Valve #2, Exp. Hall NE = SUPERVISORY
6-062-018 ISAC2 G EXP. HALL N EXIT . . MS . . Pull Station, Experimental Hall North door
TRI - for the following two addresses is located in the Exp. Hall, North West corner, North wall, 14' above floor
6-062-019 ISAC2 G OFFICES SPRINK . . . FS . . Sprinkler system for ground floor Offices, Exp. Hall NW corner, 13' above floor (piping third from top)
6-062-020 ISAC2 G OFFICES TAMPER . . . TS . . Tamper Switch on 062-019 valve = SUPERVISORY
TRI - for the following two addresses is located in the Exp. Hall, North West corner, North wall, 14' above floor
6-062-021 ISAC2 L1 OFFICES SPRINK . . FS . . Sprinkler system for L1 floor Offices, Exp. Hall NW corner, 14' above floor (piping second from top)
6-062-022 ISAC2 L1 OFFICE TAMPER . . . TS . . Tamper Switch on 062-021 valve = SUPERVISORY
TRI - for the following two addresses is located in the Exp. Hall, North West corner, North wall, 14' above floor
6-062-023 ISAC2 L2 SPRINKLERS . . . . FS . . Sprinkler system for L2 (Mechanical Penthouse), Exp. Hall NW corner, 12' above floor (bottom piping)
6-062-024 ISAC2 L2 SPRINK TAMPER . . . TS . . Tamper Switch on 062-023 valve = SUPERVISORY
6-063-001 ISAC2 L1 PS RM EAST EXIT . . MS . . Pull Station, Power Supply room #260, East Exit, South wall
6-063-002 ISAC2 L1 PS RM EAST . . . . SMK . . East side of Power Supply room #260
6-063-003 ISAC2 L1 PS RM CENTRE . . . SMK . . Centre of Power Supply room #260
6-063-004 ISAC2 L1 PS RM WEST . . . . SMK . . West side of Power Supply room #260
6-063-005 ISAC2 L1 PS RM S EXIT . . . MS . . Pull Station, Power Supply room #260, South Exit above Beam Link
6-063-006 ISAC2 L1 E CORR. S EXIT . . MS . . Pull Station, L1 East corridor, South end, East wall by Exit door
6-063-007 ISAC2 L1 COMPUTER RM 249 . . SMK . . centre of ceiling, room #249
6-063-008 ISAC2 L1 COUNT RM 3 248 . . SMK . . centre of ceiling, room #248
6-063-009 ISAC2 L1 CONTROL RM EXIT . . MS . . Pull Station, L1 Control Room #245, East wall, North of double doors
6-063-010 ISAC2 L1 COUNT RM 2 247 . . SMK . . centre of ceiling, room #247
6-063-011 ISAC2 L1 COUNT RM 1 246 . . SMK . . centre of ceiling, room #246
6-063-012 ISAC2 L1 TOP ELEV. SHAFT . . SMK . . top of Elevator shaft
6-063-013 ISAC2 L1 N CENTRE EXIT . . . MS . . Pull Station, North wall next to Exit door to Stair #2
6-063-014 ISAC2 L1 TOP N CNTR STRS . . SMK . . Stair #2 (North centre) ceiling, above top step
6-063-015 ISAC2 L1 DATA ACQ RM N . . . SMK . . ceiling, North portion of Data Acquisition room #243
6-063-016 ISAC2 L1 DATA ACQ RM S . . . SMK . . ceiling, South portion of Data Acquisition room #243
6-063-017 ISAC2 L1 NET COMP RM N . . . SMK . . ceiling, North portion of Network Computer room #130
6-063-018 ISAC2 L1 NET COMP RM S . . . SMK . . ceiling, South portion of Network Computer room #130
6-063-019 ISAC2 L1 LUNCH ROOM . . . . SMK . . ceiling, East side of of room #221, near kitchen area
6-063-020 ISAC2 L1 OPEN OFF.S WALL . . MS . . Pull Station, South wall of open office area, next to door for room #223
6-063-021 ISAC2 L1 OPEN OFFICE SE . . SMK . . ceiling of L1 Open Office area, South East quadrant
6-063-022 ISAC2 L1 OPEN OFFICE NE . . SMK . . centre of L1 Open Office area, North East quadrant
6-063-023 ISAC2 L1 OPEN OFFICE NW . . SMK . . centre of L1 Open Office area, North West quadrant
6-063-024 ISAC2 L1 OPEN OFFICE SW . . SMK . . centre of L1 Open Office area, South West quadrant
6-063-025 ISAC2 L1 NW STAIRS EXIT . . MS . . Pull Station, North wall next to Exit door to Stair #1
6-063-026 ISAC2 L1 TOP NW STAIRS . . . SMK . . Stair #1 (North West) ceiling, above top landing
6-063-027 ISAC2 L1 TITAN RM 264 . . . SMK . . centre of ceiling, room #264
PENTHOUSE - L2
6-064-001 ISAC2 L2 TOP SE STAIRS . . . SMK . . Stair #3 (South East) ceiling, above top landing
6-064-002 ISAC2 L2 SE STAIRS EXIT . . MS . . Pull Station, East wall, next to Exit door to Stair #3
6-064-003 ISAC2 L2 NORTH EMRG.EXIT . . MS . . Pull Station, North end of Emergency Escape catwalk from the Mechanical Room (L2), North wall next to
Exit door to ladder, at top of Stair #2
The West beam covers the West portion of the Accelerator Vault aiming North to South.
The Centre beam covers the middle portion of the Accelerator Vault aiming West to East.
The East beam covers the East portion of the Accelerator Vault aiming South to North.
6-065-001 ISAC2 ACC.VLT. E BEAM . . . SMK . . Accelerator Vault, East linear beam smoke detector
6-065-002 ISAC2 ACC.VLT. CNTR BEAM . . SMK . . Accelerator Vault, Centre linear beam smoke detector
6-065-003 ISAC2 ACC.VLT. W BEAM . . . SMK . . Accelerator Vault, West linear beam smoke detector
EXPERIMENTAL HALL LINEAR BEAM DETECTORS
6-066-001 ISAC2 EXP.HALL E BEAM . . . SMK . . Experimental Hall, East linear beam smoke detector.
6-066-002 ISAC2 EXP.HALL CNTR BEAM . . SMK . . Experimental Hall, Centre linear beam smoke detector.
6-066-003 ISAC2 EXP.HALL W BEAM . . . SMK . . Experimental Hall, West linear beam smoke detector.
OTHER
6-067-001 ISAC2 G RF/CRYO/EL SOL . . . CO . . Pre-action Sprinkler Solenoid, G, R.F., Cryogenic and Electrical Rooms
6-067-002 ISAC2 L1 PS/COMP RM SOL . . CO . . Pre-action Sprinkler Solenoid, L1, Power Supply and Computer Rooms
6-068-001 ISAC2 G BELLS . . . . . . . CO . . Bells
6-068-002 ISAC2 L1 & L2 BELLS . . . . CO . . Bells
6-068-003 ISAC2 STROBE LIGHT . . . . . CO . . Strobe Light, West side, above Lobby door, facing South
9-091-001 ARIEL B1 N ELEC. RM NW . . . . . SMK . . Smoke detector in the NW corner, B1 N Rm B1-09
9-091-002 ARIEL B1 N ELEC. RM SW . . . . . SMK . . Smoke detector in the SW corner, B1 N Rm B1-09
9-091-003 ARIEL B1 N ELEC. RM SE . . . . . SMK . . Smoke detector in the SE corner, B1 N Rm B1-09
9-091-004 ARIEL B1 N ELEC. RM PS . . . . . MS . . Pull Station at door, B1 N Rm B1-09
9-091-005 ARIEL B1 N PS/HV RM sw . . . . . SMK . . Smoke detector in the SW corner, B1 N Rm B1-08
9-091-006 ARIEL B1 N PS/HV RM SE . . . . . SMK . . Smoke detector in the SE corner, B1 N Rm B1-08
9-091-007 ARIEL B1 N PS/HV RM NE . . . . . SMK . . Smoke detector in the NE corner, B1 N Rm B1-08
9-091-008 ARIEL B1 N PS/HV RM NW . . . . . SMK . . Smoke detector in the NW corner, B1 N Rm B1-08
9-091-009 ARIEL B1 N PS/HV RM PS . . . . . MS . . Pull Station at door, B1 N Rm B1-08
TRI - for the following two addresses is located in the North Service Shaft, B1 Level. Access from stairwell
9-091-010 ARIEL B1 N LOBBY SPRINK . . . . FS . . Sprinkler system for B1 N Stairwell & Lobby
9-091-011 ARIEL B1 N LOBBY TAMPER . . . . TS . . Tamper Switch on 091-010 valve = SUPERVISORY
9-091-016 ARIEL G N C.S.B. NORTH DOOR . . MS . . Pull Station at North door
TRI - for the following two addresses is located in the North Service Shaft, G Level. Access from stairwell
9-091-017 ARIEL G N, SPRINKLER FLOW . . . FS . . Sprinkler system for C.S.B. room and Stairwell Lobby
9-091-018 ARIEL G N, SPRINKLER TAMPER . . TS . . Tamper Switch on 091-017 valve = SUPERVISORY
9-091-019 ARIEL G N, ALIS Rm HVAC Duct . . DS . . . ALIS rm HVAC system duct detector, on Alarm shuts off HVAC fan
9-091-020 ARIEL L1 N, ELEV. MECH.RM . . . SMK . . North Elevator (#1) Machine Room, L1 N, Room # L1-08
9-091-021 ARIEL L1 N, C.S.B. LAB NW . . . SMK . . Smoke detector in the NW corner
9-091-022 ARIEL L1 N, C.S.B. LAB SW . . . SMK . . Smoke detector in the SW corner
For East side of C.S.B. Lab detection see Linear Beam Detector: 9-098-001
TRI - for the following two addresses is located in the North Service Shaft, G Level. Access from stairwell
9-091-025 ARIEL L1 N SPRINKLER FLOW . . . FS . . Sprinkler system for Mass Separator Room
9-091-026 ARIEL L1 N SPRINKLER TAMPER . . TS . . Tamper Switch on 091-017 valve = SUPERVISORY
9-091-030 ARIEL/ISAC Link Smoke North . . SMK . . Smoke detector on ceiling, north ***
9-091-031 ARIEL/ISAC Link Smoke South . . SMK . . Smoke detector on ceiling, south ***
9-091-032 ARIEL/ISAC Link Pull Stn North . MS . . . Pull Station at north door ***
9-091-033 ARIEL/ISAC Link Pull Stn South . MS . . . Pull Station at south door *** all not active until 19 June 2017
TRIs - for the following four addresses are located in the North Elevator Mechanical Room, L1 Stairwell
9-091-056 ARIEL N ELEV. GEN.ALARM . . . . CI . . . Elevator Controls recall relay
9-091-057 ARIEL N ELEV. ALT.FLOOR . . . . CI . . . Elevator Controls recall relay
9-091-058 ARIEL N ELEV. ELEV. ROOM . . . . CI . . . Elevator Controls recall relay
9-091-059 ARIEL N ELEV. ELEV. SHAFT . . . CI . . . Elevator Controls recall relay
9-092-001 ARIEL B2 N, MECH. RM S . . . . . SMK . . B2 N Mechanical Room South Wall, B2-09
9-092-002 ARIEL B2 N, MECH. RM W . . . . . SMK . . B2 N Mechanical Room West Wall, B2-09
9-092-003 ARIEL B2 N, MECH. RM PS . . . . MS . . . B2 N Mechanical Room Pull Station at door
TRI - for the following address is located in the B2 Mechanical Room, on ceiling above the valve
9-092-004 ARIEL B2 N MECH.RM. VALVE . . . TS . . . Tamper Switch on the building Main Water Inlet Valve (near ceiling)
TRI - for the following two addresses is located on the B2 North level. Access from foot of stairwell
9-092-006 ARIEL B2 N, SPRINKLERS . . . . . FS . . . Sprinkler System for Mass Separator Room B2-08
9-092-007 ARIEL B2 N, SPRINK TAMPER . . . TS . . . Tamper Switch for 092-006 valve = SUPERVISORY
9-092-010 ARIEL B2 N ELEVATOR PIT . . . . HD . . Heat Detector in North Elevator Pit
9-092-011 ARIEL N ELEVATOR TOP . . . . . . SMK . . Smoke Detector at the top of the North Elevator shaft
9-092-015 ARIEL B2 N STAIRS LOBBY . . . . SMK . . Smoke detector at B2 North Elevator Lobby
9-092-016 ARIEL B1 N STAIRS LOBBY . . . . SMK . . Smoke detector at B1 North elevator Lobby
9-092-017 ARIEL G N STAIRS LOBBY . . . . . MS . . Pull Station on North Stairs, Ground floor
9-092-018 ARIEL G N STAIRS LOBBY . . . . . SMK . . Smoke detector at North Stairs, Ground floor
9-092-019 ARIEL L2 TOP OF N STAIRS . . . . SMK . . Smoke detector at top of North Stairs
9-093-001 ARIEL L2 N, NW AREA . . . . . . SMK . . Smoke detector NW area
9-093-002 ARIEL L2 N, STAIRS PS . . . . . MS . . Pull Station at North stairs door
9-093-003 ARIEL L2 N, NE AREA . . . . . . SMK . . Smoke detector NE area
9-093-004 ARIEL L2 NORTH CENTRE . . . . . SMK . . Smoke detector in North Centre area
9-093-005 ARIEL L2 N, BOILER RM . . . . . SMK . . Smoke detector in Boiler Room (NE area)
9-093-006 ARIEL L2 AT FILTER ROOM . . . . SMK . . Smoke detector above double doors to Filter Room
9-093-007 ARIEL L2 CENTRE BY HATCH . . . . SMK . . Smoke detector, centre area by hatch
9-093-008 ARIEL L2 FILTER RM N . . . . . . SMK . . Smoke detector Filter Room North
9-093-009 ARIEL L2 FILTER RM CNTR. . . . . SMK . . Smoke detector Filter Room Centre
9-093-010 ARIEL L2 FILTER RM S . . . . . . SMK . . Smoke detector Filter Room South
9-093-011 ARIEL L2 SE SHAFT RM . . . . . . SMK . . Smoke detector in Fan/Shaft room (SE corner)
9-093-012 ARIEL L2 SOUTH EAST . . . . . . SMK . . Smoke detector in South east area
9-093-013 ARIEL L2 SOUTH CENTRE . . . . . SMK . . Smoke detector in South Centre area
9-093-014 ARIEL L2 MECH. SOUTH WEST . . . SMK . . Smoke detector in South West area
9-093-015 ARIEL L2 SOUTH STAIRS PS . . . . MS . . Pull Station at South Stairs door
9-093-016 ARIEL L2 S, EXHAUST MONITOR RM . SMK . . Smoke detector, ceiling of Exhaust Monitoring room, L2-03
9-093-017 ARIEL L2 S, ELEV MACH. RM . . . SMK . . Smoke detector, ceiling of South Elevator Machine room, L2-02
TRI - for the following address is located on L2, by the south stairwell door
9-093-018 ARIEL L2 STAIR PRESS FAN . . . CO . . South stairwell Pressurization fan (starts on any Alarm)
9-093-019 ARIEL L2 S ELEV SHAFT TOP . . . SMK . . Smoke Detector at the top of the South Elevator shaft
9-093-020 ARIEL L2 AHU.RO23 CONTROL . . . CO . . Building Main Fan Shutdown (shuts down on any Alarm)
TRIs - for the following three addresses are located by the Main Sprinkler Supply Valve & B.F.P.'s, L2 North
9-093-027 ARIEL L2 N, BFP VLV #1 . . . . . TS . . Tamper Switch on BFP Valve #1 (upstream of 9-093-031)
9-093-028 ARIEL L2 N, BFP VLV #2 . . . . . TS . . Tamper Switch on BFP Valve #2 (upstream of 9-093-031)
9-093-031 ARIEL L2 MAIN SPRINKLER FS . . . FS . . Flow Switch for Main Sprinkler Supply (all sprinklers)
TRI - for the following two addresses is located by the Main Sprinkler Supply Valve & B.F.P.'s, L2 North
9-093-032 ARIEL L2 SPRINKLER FLOW . . . . FS . . Flow Switch for L2 sprinklers and exterior canopy sprinklers
9-093-033 ARIEL L2 SPRINK TAMPER . . . . . TS . . Tamper Switch for 093-032 valve = SUPERVISORY
9-093-035 ARIEL L2 AHUL201 DUCT SMOKE . . DS . . Duct Smoke deetector [Not shown on drawings]
TRI - for the following two addresses is located on L2 adjacent to the south stairwell door
9-093-037 ARIEL PAINT BOOTH LG_L2 FLOW . . FS . . FS for Paint Booth room G-04 (G South) & Shaft Room L2-06 (L2 SE corner)
9-093-038 ARIEL PAINT BOOTH LG_L2 TAMPER . TS . . Tamper Switch for 093-037 FS = SUPERVISORY
This Tamper Switch is on the valve which is adjacent to the Flow Switch
also see:
9-093-038 ARIEL PAINT BOOTH LG_L2 TAMPER . TS . . Tamper Switch for 093-037 FS = SUPERVISORY
This Tamper Switch is located on a valve in the NE corner of room G-04
This valve is for local emergency shutoff
9-093-056 ARIEL S ELEV. GEN.ALARM . . . . CI . . Elevator Control recall relay
9-093-057 ARIEL S ELEV. ALT. FLOOR . . . . CI . . Elevator Control recall relay
9-093-058 ARIEL S ELEV. ELEV. ROOM . . . . CI . . Elevator Control recall relay
9-093-059 ARIEL S ELEV. ELEV. SHAFT . . . CI . . Elevator Control recall relay
9-094-001 ARIEL B2 S SUMP ROOM . . . . . SMK . . Smoke detector in south sump room (foot of stairwell)
9-094-002 ARIEL B2 SOUTH LOBBY . . . . . SMK . . Smoke detector, B2 South Elevator Lobby
9-094-003 ARIEL B2 S, CORRIDOR CNTR. . . . SMK . . Smoke detector in passageway to Hot Cells & Remote Handling Bldg.
9-094-004 ARIEL B2 S, CORRIDOR WEST. . . . SMK . . Smoke detector in passageway to Hot Cells & Remote Handling Bldg.
9-094-005 ARIEL B2 SOUTH STAIRS . . . . . MS . . Pull Station on B2 at South stairs door
9-094-006 ARIEL B2 S CORRIDOR EAST . . . . MS . . Pull Station in passageway, at door to Remote Handling Bldg.
9-094-007 ARIEL B2 S, TGT ASSY E . . . . . SMK . . Smoke detector, B2 South Target Assembly Lab, East
9-094-009 ARIEL B2 S, ANTE RM N . . . . . SMK . . Smoke detector, Hot Cell Ante Room, North
9-094-010 ARIEL B2 S, ANTE RM S . . . . . SMK . . Smoke detector, Hot Cell Ante Room, South
9-094-011 ARIEL B2 S, TGT PIT W HD . . . . CI . . Heat detector, on ceiling at West end of target pit
9-094-012 ARIEL B2 S, TGT PIT E HD . . . . CI . . Heat detector, on ceiling at East end of target pit
9-094-013 ARIEL B2 S HOT CELL ACC. E . . . SMK . . Smoke detector, Hot Cell Access area (rear/north side), East
9-094-014 ARIEL B2 S HOT CELL ACC. W . . . SMK . . Smoke detector, Hot Cell Access area (rear/north side), West
9-094-015 ARIEL B2 S STORAGE . . . . . . . SMK . . Storage Area at entrance to Beam Tunnel
TRI - for the following address is located on the wall, north of the Tunnel Maze Access door
9-094-016 ARIEL B2 S TUNNEL MAZE . . . . . CI . . Pull Station inside the Tunnel Maze Access door
9-094-017 ARIEL B2 S ELEV. PIT HD . . . . HD . . Heat Detector in South Elevator Pit
TRI - for the following two addresses is located on the B2 Level, in the South stairwell
9-094-018 ARIEL B2 S, SPRINKLER FLOW . . . FS . . Sprinkler System for B2 south area
9-094-019 ARIEL B2 S, SPRINK TAMPER . . . TS . . Tamper Switch for 094-018 valve = SUPERVISORY
9-094-020 ARIEL B1 S, CHEM LAB E . . . . . SMK . . B1 South, Actinide Chem. Lab, East side
9-094-021 ARIEL B1 S, CHEM LAB W . . . . . SMK . . B1 South, Actinide Chem. Lab, West side
9-094-022 ARIEL B1 S, CORRIDOR . . . . . . SMK . . B1 South, at door to Radio-Chemisrty Lab
9-094-023 ARIEL B2 S, STAIRS P.S. . . . . MS . . . Pull Station at door to south stairs
9-094-024 ARIEL B1 S, LOBBY . . . . . . . SMK . . Smoke detector, B1 South Elevator Lobby
TRI - for the following two addresses is located in a wall hatch, accessed from the south stairwell
9-094-025 ARIEL B1 S, SPRINKLER FLOW . . . FS . . Sprinkler System for B1 south areas
9-094-026 ARIEL B1 S, SPRINK TAMPER. . . . TS . . Tamper Switch for 094-025 valve = SUPERVISORY
9-094-027 ARIEL G S, CHEM LAB E . . . . . SMK . . Ground Floor South, Chemistry Lab, East side
9-094-028 ARIEL G S, CHEM LAB W . . . . . SMK . . Ground Floor South, Chemistry Lab, West side
9-094-029 ARIEL G S, CORRIDOR . . . . . . SMK . . Ground Floor South, Smoke detector in corridor
9-094-030 ARIEL G S, STAIRS P.S. . . . . . MS . . . Pull Station Ground Floor, at South Stairs door
9-094-031 ARIEL G S, LOBBY . . . . . . . . SMK . . Smoke detector, in Elevator Lobby
9-094-032 ARIEL G S, VESTIBULE . . . . . . MS . . . Pull Station at North door to South Entrance Vestibule
TRI - for the following two addresses is located in the south service shaft, G Level, access from stairwell
9-094-033 ARIEL G S, SPRINKLER FLOW . . . FS . . Sprinkler System for Ground Floor South area
9-094-034 ARIEL G S, SPRINK TAMPER . . . . TS . . Tamper Switch for 094-033 valve = SUPERVISORY
9-094-035 ARIEL L1 S, CRANE CTRL RM . . . SMK . . L1 South, Smoke detector, ceiling of Crane Control Room
9-094-036 ARIEL L1 S, I.T. RM. . . . . . . SMK . . L1 South, Smoke detector, ceiling of IT room
9-094-037 ARIEL L1 SOUTH STAIRS . . . . . MS . . . L1 South, Pull Station at Stairs door
9-094-038 ARIEL L1 SOUTH CORRIDOR . . . . SMK . . L1 South, Smoke detector in hallway to Crane Control Room
9-094-039 ARIEL L1 SOUTH LOBBY . . . . . . SMK . . L1 South, Smoke detector in Elevator Lobby
TRI - for the following two addresses is located in the south service shaft, L1 level, access from stairwell
9-094-040 ARIEL L1 S, SPRINKLER FLOW . . . FS . . Sprinkler System for L1 Level
9-094-041 ARIEL L1 S, SPRINK TAMPER . . . TS . . Tamper Switch for 094-040 valve = SUPERVISORY
9-094-042 ARIEL L2 TOP OF S STAIRS . . . . SMK . . Smoke Detector at top of South stairs
9-094-044 ARIEL G S, ENT. VESTIBLE . . . . SMK . . Smoke detector, ceiling of Elevator Vestibule
9-095-001 ARIEL TARGET HALL BEAM W . . . . SMKB . . Linear Beam detector for West side of Hall
9-095-002 ARIEL TARGET HALL BEAM E . . . . SMKB . . Linear Beam detector for East side of Hall
CZMs - for the following two addresses are located in the Main XLS panel, B1 N Electrical Room
9-095-003 ARIEL B2 S, TNL HEAT (8) . . . . CZM - CZM in XLS-9
- module monitoring the following 8 devices -
Eight Explosion Proof Heat Detectors in the Tunnel and Maze (ARIEL B2 South).
CZM - CZM in XLS-9
9-095-004 ARIEL B2 N, MASS SEP RM
- module monitoring the following 5 devices -
Four Smoke Detectors in the Mass Separator Room (ARIEL B2 North) and
one Pull Station at the stairs door.
9-096-001 ARIEL B2 BELL Circuit B1 . . B . Bell circuit 1
9-096-002 ARIEL B1 BELL Circuit B2 . . B . Bell circuit 2
9-096-003 ARIEL G BELL Circuit B3 . . B . Bell circuit 3
9-096-004 ARIEL L2 BELL Circuit B4 . . B . Bell circuit 4
9-096-005 ARIEL L1 BELL Circuit B5 . . B . Bell circuit 5
9-096-006 ARIEL G BELL Circuit B6 . . B . Bell circuit 6
9-096-007 ARIEL B1 BELL Circuit B7 . . B . Bell circuit 7
9-096-008 ARIEL B2 BELL Circuit B8 . . B . Bell circuit 8
9-097-001 ARIEL B2 STROBE Circuit S1 . S . Strobe Light
9-097-002 ARIEL B1 STROBE Circuit S2 . S . Strobe Light
9-097-003 ARIEL G STROBE Circuit S3 . S . Strobe Light, North
9-097-004 ARIEL G STROBE Circuit S4 . S . Strobe Light, South
9-097-005 ARIEL L2 STROBE Circuit S5 . S . Strobe Light
9-098-001 ARIEL L1 East CSB LAB BEAM . SMKB . Linear beam detector on east side going south to north.
PLANT SERVICES Bldg. XLS-12 located in Mech. Serv. Workshop
PMI-2 in XLS-12
12-110-001 Work Space 101 - South man door. . . . MS
12-110-002 Office 108 . . . . . . . . . . . . . . SMK/HD
12-110-003 Work Space 101 - South West. . . . . . HD
12-110-004 Work Space 101 - South East. . . . . . HD
12-110-005 Work Space 101 - North West. . . . . . HD
12-110-006 Work Space 101 - North East. . . . . . HD
12-110-007 Pipe Fitters 102 - West Man Door . . . PS
12-110-008 Pipe Fitters 102 - West. . . . . . . . HD
12-110-009 Pipe Fitters 102 - East. . . . . . . . HD
12-110-010 Pipe Fitters 102 - East Man Door . . . PS
12-110-011 Compressor room 110. . . . . . . . . . HD
12-110-012 Liquid Helium Plant Mezzanine - SW . . HD
12-110-013 Electrical Shop 103 Mezzanine - W . . SMK/HD
12-110-014 Electrical Shop 103 West . . . . . . . SMK/HD
12-110-015 Electrical Shop 103 East . . . . . . . SMK/HD
12-110-016 Electrical Shop 103 East Man Door. . . MS
12-110-017 Liquid Helium Plant - West man Door. . MS
12-110-018 Liquid Helium Plant - South. . . . . . HD
12-110-019 Liquid Helium Plant - North. . . . . . HD
12-110-020 Liquid Helium Plant Mezzanine - SE . . HD
12-110-021 Liquid Helium Plant Mezzanine - NE . . HD
12-110-022 Office 107A . . . . . . . . . . . . . SMK/HD
12-110-023 Liquid Helium Plant North Man Door . . MS
12-110-024 Office 107B . . . . . . . . . . . . . .SMK/HD
12-110-025 Office 107C . . . . . . . . . . . . . .SMK/HD
12-110-026 Office 107 Hallway . . . . . . . . . . SMK/HD
12-110-027 Office 107 Hallway East Man Door . . . MS
12-110-028 Change Room 104 . . . . . . . . . . . .HD
AC FAIL OR BROWNOUT. . . . . . . . Primary AC power is missing or below the brownout level; the System is running on battery backup.
AUX PWR CLASS A FAIL NEG LOOP. . . The negative side of the CZM-1 power circuit is open.
AUX PWR CLASS A FAIL POS LOOP. . . The positive side of the CZM-1 power circuit is open.
AUX POWER VOLTAGE LOW. . . . . . . PSR-1 24V output is overloaded.
BATTERY BACKUP INVALID . . . . . . A battery is connected, but not selected in the CSG-M.
BATTERY FUSE/WIRING OPEN . . . . . The battery is not connected, or the battery fuse is blown.
CLASS A LOOP TROUBLE . . . . . . . If Class A: The initiating circuit at this module address has an open. If Class B: Wired zones are missing the Class A jumpers.
CONFIGURATION ERROR. . . . . . . . A configuration error where the PSR-1 switch setting doesn't agree with the CSG-IIA.
DEFAULT ALARM BUS ACTIVE . . . . . PSR-1 remote panel has its local alarm bus (Fire Alarm) active.
DEFAULT TROUBLE ACTIVE . . . . . . PSR-1 remote panel has its local trouble bus active.
DEVICE COMMUNICATION ERROR . . . . An analog device whose response has failed error checking.
DEVICE DETECTED WAVEFORM ERROR . . An analog device reports this trouble if it receives an unknown polling waveform.
DEVICE LED TURNED ON . . . . . . . A device LED was turned on from the Control menu of the XLS.
DEVICE MULTIPLE RESPONSE . . . . . Two or more analog devices at the same address have reported during normal supervision.
DEVICE RECEIVER ERROR. . . . . . . An analog device reports this trouble if it receives an incorrect analog transmission.
GROUND FAULT MINUS . . . . . . . . The ground fault detection circuit has a low impedance to the negative side of one of the field wiring circuits.
GROUND FAULT PLUS. . . . . . . . . The ground fault detection circuit has a low impedance to the positive side of one of the field wiring circuits.
INCORRECT DEVICE ID. . . . . . . . An analog device whose type or usage does not agree with the CSG-M assignment at that address.
INPUT DEVICE NOT RESPONDING. . . . A device assigned in the CSG-M is not reporting at its address.
INPUT DEVICE RESPONSE TOO LOW. . . An analog device whose input is off-normal. EOL missing on TRI or CZM-1 , CZM-i input power missing, or defective device.
INPUT DISARMED . . . . . . . . . . An initiating device was disarmed through the Control menu.
LOOP NOISE TROUBLE . . . . . . . . The ALD-2 at this address has determined that excessive noise exists at this analog loop and that the device cannot be
communicated with.
LOSS OF 24V INPUT POWER. . . . . . A CZM-4- has lost its 24 VDC input.
MODULE COMMUNICATION FAILURE . . . When module communications are interrupted, and then restored, all module addresses affected report this trouble.
MODULE NOT RESPONDING. . . . . . . The module assigned in the CSG-M at this address is not responding.
MODULE RAM FAILURE . . . . . . . . The CRM-4, CSM-4, or CZM-4 at this address has determined that its internal RAM is not operating properly.
MODULE ROM FAILURE . . . . . . . . The module at this address has a ROM checksum failure.
MORE THAN 127 ALARMS . . . . . . . The System alarm queue is full, and more alarms have been received.
MORE THAN 127 SECURITY ALARM . . . The System security condition queue is full, and more security conditions have been received.
MORE THAN 127 SUPERV TROUBLE . . . The System Supervisory queue is full, and more supervisories have been received.
MORE THAN 127 TROUBLES . . . . . . The System trouble queue is full, and more troubles have been received,
MULTIPLE RESPONSE ANALOG POLL. . . Two or more analog devices at the same address have reported during an analog data request.
NETWORK DISABLED . . . . . . . . . The remote PSR-1 has its network disabled switch set incorrectly.
PRINTER OFF LINE/FAULT . . . . . . A supervised printer is not responding.
PRINTER OUT OF PAPER . . . . . . . The TSP-40 has run out of paper.
RELAY COIL OPEN. . . . . . . . . . The relay coil at this address is open.
RELAY DISARMED . . . . . . . . . . The relay at this address has been disarmed from the Control menu.
RELAY DRIVER INOPERATIVE . . . . . The relay on the CRM-4 or CSM-4 at this address does not operate when commanded to energize.
RELAY SUPERVISION FAILURE. . . . . The relay at this address has a coil failure.
SIGNAL CIRCUIT DISARMED. . . . . . The IAC at this address was disarmed from the Control panel.
SIGNAL CKT LOOP SHORTED. . . . . . The IAC at this address is shorted, or the EOL device is the wrong value, or the indicating appliances are not polarized or
are connected backwards.
SIGNAL CKT SUPERVISION LOOP OPEN . The IAC at this address has a broken wire or missing EOL device.
SIGNAL MOD A/D COVERT FAIL . . . . The CSM-4 at this address has a failed analog-to-digital converter.
SIGNAL MODULE ZONE CODE. . . . . . Zone code failure on the CSM-4 module.
SYSTEM SIGNAL POWER FAILURE. . . . A CSM-4 has lost power to its output circuits.
TROUBLE TYPE NOT DEFINED . . . . . Unspecified trouble has been received from this address.
UNSPECIFIED DEVICE RESPONDING. . . An analog device has reported at an address not assigned in the CSG-M.
UNSPECIFIED MODULE RESPONDING. . . A module has reported at an address not assigned in the CSG-M.
WARM RESET . . . . . . . . . . . . The hardware reset input to the XLS was used.
WATCHDOG CIRCUIT TRIGGERED . . . . The watchdog circuit on the MMB-1 was triggered.
ZONE LOOP OPEN . . . . . . . . . . Broken wire or missing EOL device at this address on a CZM-4 zone.
ZONE POWER LOSS. . . . . . . . . . The CZM-4 zone at this address has lost its 24 volt input.
TRI - two TRI's for the following four addresses , in MOB room 42, on ceiling
1-035-006 MOB G UNDER AUDITORIUM BACKFLOW . TS . Backflow preventer service valves for the above - Supervisory
- The following 9 addresses are in functional order, not in numerical order -
TRI-D - in room 42, west wall - module monitoring -051 & -052
1-035-051 MOB G Sprinkler Backflow Inlet. . TS . Backflow preventer inlet valve - Supervisory
1-035-052 MOB G Sprinkler Backflow Outlet . TS . Backflow preventer outlet valve - Supervisory
TRI-D - in room 42, on ceiling - module monitoring -053 & -054
1-035-054 MOB G MAIN SPRINKLER TAMPER . . . TS . Main Sprinkler Valve tamper switch - Supervisory
TRI-D - in room 42, on ceiling - module monitoring -057 & -058
1-035-053 MOB G SPRINKLER FLOW. . . . . . . FS . Ground floor Sprinklers
1-035-057 MOB G Sprinkler Tamper. . . . . . TS . Main Sprinkler Valve for 1-035-053 - Supervisory
TRI-D - in room 42, on ceiling - module monitoring -055 & -056
1-035-055 MOB L1 SPRINKLER FLOW . . . . . . FS . L1 Floor Sprinklers
1-035-058 MOB L1 Sprinkler Tamper . . . . . TS . Valve for 1-035-055 - Supervisory
TRI-S - in room 42, west wall - module monitoring -059
1-035-059 MOB G FIRE HOSE STANDPIPE FLOW. . FS . Water flow from any of the 7 hose cabinets - Supervisory
1-035-056 MOB FIRE HOSE CAB. TAMPER . . . . TS . Fire Hose Cabinets Main Valve for 1-035-059 - Supervisory
---------------------------------------
2-001-025 HAZ.MAT.BLDG. SPRINKLERS . . FS . . Sprinkler water flow, module in Lobby on West wall
---------------------------------------
2-001-060 MHESA B1 SPRINKLER TAMPER . TS . . Either of two Backflow Preventer Valves located in MHESA B1 room 03
---------------------------------------
2-002-050 RH G WORKSHOP PULL STNS . . CZM . . 4 pull stations, plus 1 sprinkler device
---------------------------------------
2-002-055 RH B1 SPRINKLERS - monitoring the following 2 devices -
Sprinkler system Water Flow and Tamper switches
---------------------------------------
TS - TROUBLE
2-002-058 RH B2 SPRINKLERS - monitoring the following 2 devices -
Sprinkler system Water Flow and Tamper switches
---------------------------------------
TS - TROUBLE
B1 floor, room 14 (CP42 Power Supply room)
B1 floor, room 24 (service room)
---------------------------------------
3-019-016 CA B1 SPKLR TAMPER . . . . TS . . Tamper switch for 3-019-015 = SUPERVISORY
---------------------------------------
3-019-018 CA B1 TR30 PS RM SPKL TS . TS . . Tamper switch for 3-019-017 = SUPERVISORY
---------------------------------------
---------------------------------------
3-019-021 CA B1 MAIN SPRINK.SUPPLY . FS . . Main Sprinkler Supply, ALARM
---------------------------------------
. . PS . . Low Pressure switch , TROUBLE
. . TS . . Tamper Switch on main supply line , TROUBLE
3-019-025 CA G N. SPKLR TAMPER . . . TS . . Tamper switch for 3-019-024 = SUPERVISORY
---------------------------------------
3-019-027 CA G S. SPKLR TAMPER . . . TS . . Tamper switch for 3-019-026 = SUPERVISORY
---------------------------------------
3-019-030 CA G LOAD BAY E. SPKL TS . .TS . . Tamper switch for 3-019-029 = SUPERVISORY
---------------------------------------
3-019-032 CA L1 S. SPKLR TAMPER . . . TS . . Tamper switch for 3-019-031 = SUPERVISORY
---------------------------------------
3-019-034 CA L1 FLR N. SPKLR TS . . . TS . . Tamper switch for 3-019-033 = SUPERVISORY
---------------------------------------
3-019-036 CA L2 N. SPRINKLR TAMPER . TS . . Tamper switch for 3-019-035 = SUPERVISORY
---------------------------------------
- for the following two addresses, CA B1 Room 30 North wall East -
3-019-046 CA B1 MAIN BFP VLVS TS . . . TS . . Two tamper switches on the back-flow preventer service valves = SUPERVISORY
---------------------------------------
3-020-033 CA L2 S. SPKLR TAMPER . . . TS . . L2 South Penthouse, Sprinkler Tamper, near North door and AHU-4 = SUPERVISORY
4-027-003 RCA3 B2 SPRINKLER TAMPER . . TS . . sprinkler valve tamper switch for 4-027-002
---------------------------------------
4-027-009 RCA3 B1 SPRINKLER TAMPER . . TS . . sprinkler valve tamper switch for 4-027-008
---------------------------------------
---------------------------------------
4-027-012 RCA3 G SPRINKLER TAMPER . . TS . . sprinkler valve tamper switch for 4-027-011
---------------------------------------
4-027-014 RCA3 L1 SPRINKLER TAMPER . . TS . . sprinkler valve tamper switch for 4-027-013
---------------------------------------
4-028-015 RCA3 L2 SPRINKLER TAMPER . . TS . . sprinkler valve tamper switch for 4-028-014
---------------------------------------
---------------------------------------
5-051-018 ISAC EXPHAL JAN SPRNK TS . . .TS . . Tamper switch for 051-017 = SUPERVISORY
---------------------------------------
5-051-022 ISAC EXPHAL G,NE SPRNK TS . . TS . . Tamper switch for 051-021 = SUPERVISORY
---------------------------------------
Alarms if any sprinkler water flows for more than 45 seconds. Switch cover off = TROUBLE
---------------------------------------
5-051-024 ISAC EXPHAL MAIN SPRNK TS . . TS . . ISAC Exp. Hall North East Corner.
TWO valves in series with the Main supply line, either side of the backflow preventer.
Either Tamper switch operated = SUPERVISORY
Either Tamper switch cover off = TROUBLE
---------------------------------------
Main water supply valve for the ISAC buildings.
Tamper switch operated = SUPERVISORY
Tamper switch cover off = TROUBLE
---------------------------------------
5-051-030 ISAC TMB B2 LOBBY SPNK TS . . TS . . Tamper Switch for 051-029 = SUPERVISORY
---------------------------------------
---------------------------------------
---------------------------------------
---------------------------------------
---------------------------------------
5-051-041 ISAC TMB B1 LOBBY SPNK TS . . TS . . Tamper Switch for 051-040 = SUPERVISORY
---------------------------------------
Low Water Pressure switch on the Main Supply Line.
Low Pressure = SUPERVISORY
Switch cover off = TROUBLE
---------------------------------------
---------------------------------------
5-052-028 ISAC TMB G MAT.BAY SPK TS . . TS . . Tamper Switch for 052-027 = SUPERVISORY
---------------------------------------
5-052-038 ISAC TMB PENTHOUSE SPK TS . . TS . . Tamper Switch for 052-037 = SUPERVISORY
---------------------------------------
5-052-049 ISAC TMB L1 DESOFF SPK TS . . TS . . Tamper Switch for 052-048 = SUPERVISORY
---------------------------------------
---------------------------------------
6-062-006 ISAC2 G RF/CRYO/EL TAMPR . . TS . . Tamper switch for 062-005 = SUPERVISORY
---------------------------------------
---------------------------------------
6-062-010 ISAC2 L1 PS/COMP TAMPER . . . TS . . Tamper switch for 062-009 = SUPERVISORY
---------------------------------------
6-062-012 ISAC2 G VLT/LABS TAMPER . . . TS . . Tamper switch for 062-011 = SUPERVISORY
---------------------------------------
6-062-015 ISAC2 G EXP HALL TAMPER . . . TS . . Tamper switch for 062-014 = SUPERVISORY
---------------------------------------
6-062-017 ISAC2 G BKFLOW PREV TS2 . . . TS . . Exp Hall NE, Valve on downstream side of backflow preventer = SUPERVISORY
---------------------------------------
6-062-020 ISAC2 G OFFICES TAMPER . . . TS . . Tamper switch for 062-019 = SUPERVISORY
---------------------------------------
6-062-022 ISAC2 L1 OFFICE SPRNK TS . . TS . . Tamper switch for 062-021 = SUPERVISORY
---------------------------------------
6-062-024 ISAC2 L2 SPRINK TAMPER . . . TS . . Tamper switch for 062-023 = SUPERVISORY
---------------------------------------
6-067-002 ISAC2 L1 PS/COMP RM SOL . . . CO . . pre-action solenoid from XLS-6, Trouble only
7-013-020 SDF G MAIN SPRNK SUP TS #2 . . TS . . Main Sprinkler supply shutoff valve = SUPERVISORY
---------------------------------------
7-013-022 SDF GRND BACKFLOW VALVE #2 . . TS . . Backflow preventer valve #2 = SUPERVISORY
---------------------------------------
CO . . Switch cover off = TROUBLE
7-013-024 SDF G FLOOR SPRINKLER VALVE . TS . . Ground floor sprinklers shutoff valve (for 013-023) = SUPERVISORY
---------------------------------------
CO . . Switch cover off = TROUBLE
7-013-026 SDF LEVEL 1 SPRINKLER VALVE . TS . . Level 1 floor sprinklers shutoff valve (for 013-025) = SUPERVISORY
---------------------------------------
CO . . Switch cover off = TROUBLE
7-013-028 SDF CANOPY SPRINKLER VALVE . TS . . Canopy sprinklers shutoff valve = SUPERVISORY
---------------------------------------
All Valves and Flow Switches are located in the Water Supply Room (west side, north end).
TRI's - for the following 11 addresses are located in the Water Supply Room, above the door.
8-041-016 ECOMP 2ND FL SPRINKLER VALVE . . TS . . Tamper switch on valve for 8-041-015 = SUPERVISORY
---------------------------------------
8-041-018 ECOMP COMP RM SPRINK VALVE . . . TS . . Tamper switch on valve for 8-041-017 = SUPERVISORY
---------------------------------------
8-041-020 ECOMP G SPRINKLER VALVE . . . . TS . . Tamper switch on valve for 8-041-019 = SUPERVISORY
---------------------------------------
8-041-022 ECOMP CANOPY SPRINKLER VALVE . . TS . . Tamper switch on valve for 8-041-021 = SUPERVISORY
8-041-023 ECOMP CANOPY SPRINKLER LOW AIR . CI . . Canopy, Dry system low air pressure = TROUBLE
---------------------------------------
---------------------------------------
8-041-025 ECOMP SPRINKLER MAIN VALVE . . . TS . . Tamper switch on MAIN WATER SUPPLY valve = SUPERVISORY
9-091-010 ARIEL B1 N LOBBY SPRINK . . . . FS . . Sprinkler system for B1 N Stairwell & Lobby
9-091-011 ARIEL B1 N LOBBY TAMPER . . . . TS . . Tamper Switch on 091-010 valve = SUPERVISORY
---------------------------------------
9-091-017 ARIEL G N, SPRINKLER FLOW . . . FS . . Sprinkler system for C.S.B. room and Stairwell Lobby
9-091-018 ARIEL G N, SPRINKLER TAMPER . . TS . . Tamper Switch on 091-017 valve = SUPERVISORY
---------------------------------------
9-091-025 ARIEL L1 N SPRINKLER FLOW . . . FS . . Sprinkler system for Mass Separator Room
9-091-026 ARIEL L1 N SPRINKLER TAMPER . . TS . . Tamper Switch on 091-017 valve = SUPERVISORY
---------------------------------------
9-092-004 ARIEL B2 N MECH.RM. VALVE . . . TS . . . Tamper Switch on the building Main Water Inlet Valve (near ceiling)
---------------------------------------
9-092-006 ARIEL B2 N, SPRINKLERS . . . . . FS . . . Sprinkler System for Mass Separator Room B2-08
9-092-007 ARIEL B2 N, SPRINK TAMPER . . . TS . . . Tamper Switch for 092-006 valve = SUPERVISORY
---------------------------------------
9-093-027 ARIEL L2 N, BFP VLV #1 . . . . . TS . . Tamper Switch on BFP Valve #1 (upstream of 9-093-031)
9-093-028 ARIEL L2 N, BFP VLV #2 . . . . . TS . . Tamper Switch on BFP Valve #2 (upstream of 9-093-031)
9-093-031 ARIEL L2 MAIN SPRINKLER FS . . . FS . . Flow Switch for Main Sprinkler Supply (all sprinklers)
---------------------------------------
9-093-032 ARIEL L2 SPRINKLER FLOW . . . . FS . . Flow Switch for L2 sprinklers and external canopy sprinklers
9-093-033 ARIEL L2 SPRINK TAMPER . . . . . TS . . Tamper Switch for 093-032 valve = SUPERVISORY
---------------------------------------
9-093-037 ARIEL PAINT BOOTH LG_L2 FLOW . . FS . . FS for Paint Booth room G-04 (G South) & Shaft Room L2-06 (L2 SE corner)
This Tamper Switch is on the valve which is adjacent to the Flow Switch
also see:
9-093-038 ARIEL PAINT BOOTH LG_L2 TAMPER . TS . . Tamper Switch for 093-037 FS = SUPERVISORY
This Tamper Switch is located on a valve in the NE corner of room G-04
This valve is for local emergency shutoff
---------------------------------------
9-094-018 ARIEL B2 S, SPRINKLER FLOW . . . FS . . Sprinkler System for B2 south area
9-094-019 ARIEL B2 S, SPRINK TAMPER . . . TS . . Tamper Switch for 094-018 valve = SUPERVISORY
---------------------------------------
9-094-025 ARIEL B1 S, SPRINKLER FLOW . . . FS . . Sprinkler System for B1 south areas
9-094-026 ARIEL B1 S, SPRINK TAMPER. . . . TS . . Tamper Switch for 094-025 valve = SUPERVISORY
---------------------------------------
9-094-033 ARIEL G S, SPRINKLER FLOW . . . FS . . Sprinkler System for Ground Floor South area
9-094-034 ARIEL G S, SPRINK TAMPER . . . . TS . . Tamper Switch for 094-033 valve = SUPERVISORY
---------------------------------------
9-094-040 ARIEL L1 S, SPRINKLER FLOW . . . FS . . Sprinkler System for L1 level area
9-094-041 ARIEL L1 S, SPRINK TAMPER . . . TS . . Tamper Switch for 094-040 valve = SUPERVISORY
1-035-045 MOB L1 ELEV MACHINE RM . . . SMK P . . L1 floor, Elevator Lobby, inside door of Elevator machine control room
[can be tested from L1 level]
between car and door frame, (label on ground floor door frame)
[can be tested from Ground level]
[can be tested only with shaft pit access *]
[can be tested only from top of car *]
[can be tested from Ground level *]
[can be tested from Ground level *]
[can be tested only from top of car *]
[can be tested from inside car]
[can be tested only from top of car *]
[can be tested only from top of car *]